8
24V
24V
GND
GND
Door switch
connections
T3-3 (GND)
and
T3-5 (DRSW)
T3-4 (24V)
and
T3-5 (DRSW)
Jumper
JP1
*25*0*
(default)
*25*1*
Open door
switch
activates
alarm
Open door
switch
activates
alarm
Closed door
switch
activates
alarm
Closed door
switch
activates
alarm
Programming
DOOR SWITCH INPUT
5. INSTALLATION
5.1 GENERAL
Installation of the Crypto-Lock requires
mounting the Keypad and Control Panel,
connecting the Keypad, AC power,
external lock, and a door switch (required
to utilize door monitoring functions) to the
Control Panel, and installing the batteries
(optional) in the Control Panel.
Programming includes setting the valid PIN
code, open duration time, invalid PIN
penalty time, and options for activating
door propped and forced door alarms and
the anti-tailgating function. Default values
are provided for all of these functions
except the PIN code.
5.2 INSTALLATION PROCEDURE
1. Mount the Keypad approximately 36 to
44 inches above the deck on the
unsecured side of the door. Use the
template at the end of this manual to mark
and drill holes. If the keypad is to be flush
mounted a ¾” hole or recess at least ¼”
deep must be prepared in the mounting
service to provide clearance for the cable
grommet on the rear of the keypad. (See
template on page 1.)
2. Mount the electric lock, strike and/or
magnet according to the manufacturer's
instructions.
3. Mount the Control Panel on the secure
side of door using the four mounting holes.
(See diagram on page 18.)
Note: All cables passing through holes
made in enclosure must be protected from
chafing. Route all cables to avoid the
battery compartment in the bottom-left of
the Control Panel.
4. Connect the Keypad to the Control
Panel as shown in Figure 5-1. Twenty feet
of cable is supplied with the Keypad. The
Keypad can be located up to 100 feet from
Control Panel using additional cable.
(Requires eight conductors, #22 or larger).
6. Connect the electric lock as shown in
Figure 5-1.
7. If used, connect an external Release
Button (not supplied), and external 24Vdc
annunciator or horn (not supplied), as
shown in Figure 5-1. Note that an internal
horn in the Control Panel will sound when
the Keypad's # button is pressed and for
various alarm functions.
8. If the Door Propped Alarm, Forced Door
Alarm or Anti-Tailgating functions will be
used, connect the door switch or
transducer to the Control Panel as shown
in Figure 5-1. This input can be configured
to accept various input signals as outlined
in the Table below.
9. If the Auxiliary Alarm Output is to be
utilized connect the external system to T5-
1 (Common) and either T5-2 (Normally
Open) or T5-3 (Normally Closed) as
appropriate. If a lock monitoring switch will
be monitored connect it to T3-6 and T3-7
and remove the jumper from JP2. If a lock
monitoring switch will not be used verify
that a jumper is installed on JP2 (JP2
shunts the lock switch input terminals T3-6
and T3-7).
10. Install and connect the batteries as
shown in Figure 5-1 using the two supplied
Summary of Contents for Crypto Lock CC-8521BN
Page 1: ...1 Crypto Lock CC 8521BN 7 17 Access Control System INSTRUCTION MANUAL MONITEQ Inc...
Page 2: ...2...
Page 16: ...16...
Page 18: ...18...
Page 19: ...19...