battery cables.  Use only 12V, 7AH re-
chargeable sealed batteries. (Moniteq 
Type CC-BATT or equivalent.) 

 
11. Connect the AC line cord to the Control 
Panel as shown in diagram below. 

5.3 POWER SUPPLY SETTINGS 

1. Connect the power cable to an 
appropriate source of 115 Vac 50/60 Hz 
power and verify that the UNREG 24VDC 
indicator in the Control Panel illuminates. 
2. MODE Switch 

– In the DIRect position 

24Vdc from the power supply is applied 
directly to the lock. This provides up to 16 
A of “in-rush” current to initially open the 
lock and then up to 2A continuous 
thereafter. Some locks including the 
Sargent-Greenleaf BRUTE can be 
damaged if powered for more than 15 
seconds with unlimited current. In the LIMit 
position up to 16A of current is available to 

initially open the lock but after the lock is 
open the current is limited to approximately 
0.3A which is sufficient to hold the lock 
open for longer periods without damaging 
it. When using the BRUTE lock we 
recommend using the LIMit position if there 
is a possibility that the lock will be held 
open for more than 15 seconds. If the 
Brute lock will not be activated for more 
that 15 seconds the mode switch can be 
safely set to the DIRect position. 
 
 
 

 

 

AC LINE

CORD

POWER

LINE

FILTER

TRANS-

FORMER

CC-8521BN
MAIN PCB

T4-2

T4-3

T4-1

TB1

CC-8521BN, AC POWER COMPARTMENT WIRING DIAGRAM

FUSE

BLU

BLU

GRN/YEL

BRN

BRN

BLK

WHT

GRN

WHT

ORG

ORG

1

5

4

2

3

Summary of Contents for Crypto Lock CC-8521BN

Page 1: ...1 Crypto Lock CC 8521BN 7 17 Access Control System INSTRUCTION MANUAL MONITEQ Inc...

Page 2: ...2...

Page 3: ...2 CONTROL PANEL 7 5 INSTALLATION 8 5 1 GENERAL 8 5 2 INSTALLATION PROCEDURE 8 5 3 POWER SUPPLY SETTINGS 9 6 1 PROGRAMMING 11 6 1 GENERAL 11 6 2 PROGRAMMING INSTRUCTIONS 11 6 2 1 INITIAL SETTINGS 11 6...

Page 4: ...noring all keypad entries for 3 to 60 seconds after an invalid digit is entered Further if five or more successive invalid PINs are entered the penalty time is set to 60 seconds until the valid PIN is...

Page 5: ...d Alarm Horn Output KEYPAD WITH STATUS LED REMOTE RELEASE BUTTON not supplied Door sensor Stand by Batteries Built in Horn and Release Buttom Ship s Central Alarm System Output Features 3 4 5 or 6 dig...

Page 6: ...3 to 60 seconds set to 60 seconds after five invalid PIN attempts Remote release input Dry contact closure Door monitoring functions Door propped open alarm forced door alarm anti tailgating Keypad D...

Page 7: ...rogramming codes Key Used as a delimiter for programming codes and parameters Key Used to terminate the programming mode Green LED indicator Programming mode Flashes continuously After a valid program...

Page 8: ...the secure side of door using the four mounting holes See diagram on page 18 Note All cables passing through holes made in enclosure must be protected from chafing Route all cables to avoid the batter...

Page 9: ...ent Greenleaf BRUTE can be damaged if powered for more than 15 seconds with unlimited current In the LIMit position up to 16A of current is available to initially open the lock but after the lock is o...

Page 10: ...TERY GROUND HORN T3 GROUND EXT RELEASE REQUEST TO EXIT Door Switch see table above DOOR SWITCH GROUND O R G W H T O R G 24 VDC 1 2 3 4 5 6 7 8 7 8 9 10 7 8 9 1 2 3 4 5 6 10 11 GROUND LOCK SWITCH GROUN...

Page 11: ...3 N 15 to 255 sec 0 Door Closed Door Closed Forced Door Alarm 24 N 0 Off 1 On Off Door Switch Sense 25 N See Table 6 2 PROGRAMMING INSTRUCTIONS Enter the Programming Mode by pressing the PROGRAM MODE...

Page 12: ...ion time enter 20 N where N is from 5 to 60 seconds Anti Tailgating The Anti Tailgating mode is provided to prevent the door from being re opened a second time during the Open Duration time period Thi...

Page 13: ...entering the valid PIN code on the Keypad will release the door The internal Release Button on the Control Panel can be used by an attendant to release the lock from a location on the secure side of...

Page 14: ...5 1 2 and 3 The relay controlling these contacts is activated continuously when a The door switch input T3 5 and T3 6 indicates that the door is ajar and b The Lock Switch Input T3 7 and T3 8 is open...

Page 15: ...15 CRYPTO LOCK Model CC 8421BN Keypad Mounting Template 3 5 8 4 5 8 3 4 D cable grommet Pilot holes Threaded inserts for 8 32 screw or threaded rod Keyhole for 8 screws 8 KEY PAD INSTALLATION TEMPLATE...

Page 16: ...16...

Page 17: ...17 9 CONTROL PANEL MOUNTING DIAGRAM 5 28 14 75 13 5 12 3 38 Mounting holes for 3 8 studs 4 places 1 4 Aluminum Mounting Bars...

Page 18: ...18...

Page 19: ...19...

Page 20: ...warranty is void in cases of abuse misuse mishandling modification or repair by unauthorized persons This warranty is given in lieu of all other warranties expressed or implied Moniteq is not liable...

Reviews: