[20]
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop
Default
:
3
Description
:
Setup the action when overload occurs
4.
O. L. Set Point
:
Range
:
1~31
0.1~20.0(A)
0.1~30.0(A)
0.1~40.0(A)
0.1~50.0(A)
0.1~60.0(A)
0.1~75.0(A)
0.1~80.0(A)
0.2~100.0(A)
0.3~150.0(A)
0.4~200.0(A)
5.0~250.0(A)
6.0~300.0(A)
8.0~400.0(A)
10.0~500.0(A)
12.0~600.0(A)
14~700.0(A)
15.0~750.0(A)
16.0~800.0(A)
18.0~900.0(A)
20.0~1000.0(A)
24.0~1200.0(A)
30.0~1500.0(A)
32.0~1600.0(A)
40.0~2000.0(A)
50.0~2500.0(A)
60.0~3000.0(A)
64.0~3200.0(A)
80.0~4000.0(A)
100.0~5000.0(A)
120~6000(A)
Description
:
When current is above setting, the controller outputs trip signal, setup range is
related to the CT ratio.
5.
Overload Delay
:
Setting
:
10~300(Second)
Default
:
40
Description
:
When overload occurres, timer starts before activating protection
6.
Short Detect
:
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates AC short protection
7.
Short protect:
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop)
Default
:
4
Description
:
Setup the action when AC short occurs
8.
Short Set Point
:
Setting
:
1~31
1~5(A)
2~10(A)
3~15(A)
4~20(A)
6~30(A)
8~40(A)
10~50(A)
12~60(A)
15~75(A)
16~80(A)
20~100(A)
30~150(A)
40~200(A)
50~250(A)
60~300(A)
80~400(A)
100~500(A)
120~600(A)
150~750(A)
160~800(A)
180~900(A)
200~1000(A) 240~1200(A)
300~1500(A)
320~1600(A)
400~2000(A)
500~2500(A) 600~3000(A)
640~3200(A)
800~4000(A)
1000~5000(A)
Description
:
When
current
is
above
the setting, controller outputs trip signal, setup range is
related to the CT ration setup.
9.
Short Delay
:
Setting
:
0.1~1.0(Second)