background image

[4] 

 

D.

 

Operation Rotary Switchs

 

 

1.

 

Manual

In manual mode, the LCD shows pre-heat function; after pre-heat, engine starts 

immediately. If engine fails to start, the GTR-620 returns to the OFF mode. The pre-heat 

state may not perform, if parameter setting is disabled.

 

If Pre-fuel is activated, the fuel 

outputs before crank procedure.

 

 

2.

 

AUTO

In the Auto mode, the GTR-620 starts the engine by ATS signal and then the LCD 

shows preheat, if pre-heat function is enabled. After pre-heat, the engine starts to crank. If 

engine fails to start, the system returns to the pre-heat state and then start to crank the 

engine again. For example, if the conditions and parameter settings are given as follows: 

1.stop duration is 10 seconds, crank attempt is 3 times. The engine cranks for 10 seconds 

and then rest for 10 seconds, after 3 attempts, the LCD shows the over crank and triggers 

the alarm. 

 

 

3.

 

OFF

Switch to OFF stops the engine and then “stop” appears on the LCD. The idle also 

appears on the LCD, if the idle function is enabled. After 10 seconds of delay (depends on 

the setting), the engine stops completely and idle icon disappears.

 

 

E.

 

Rear connectors

 

 

Pin 

Description 

Code 

B+ 

Battery - 

B- 

Ground 

GND 

Crank output 

Crank 

Fuel pump output

 

Fuel 

Stop output

 

Stop 

Output 3 

Out.3 

Output 2 

Out.2 

10 

Output 1 

Out.1 

11 

Output 1 

 

12 

Output 0 

Out.0 

13 

Output 0 

 

18 

Input 4 

IN.4 

19 

Input 3 

IN.3 

20 

Input 2 

IN.2 

Summary of Contents for GTR-620

Page 1: ...1 GTR 620 User manual T E L 0 4 2 2 3 8 0 6 9 8 F A X 0 4 2 2 3 8 0 8 9 1 Web Site http www monicon com t w E m a i l s a l e s m o n i c o n c o m t w...

Page 2: ...onnector 26 detects signal from ATS switch C Setup Keypad 1 In password entry mode this keypad switches to next digit 2 Under PARAMETER setting this keypad switches to the next parameter 1 In password...

Page 3: ...000 1 In CODE entry mode this keypad decreases the value 2 Under the PARAMETER setting mode this keypad decreases the setting Enter or exit the parameter setting mode Confirm and save the settings The...

Page 4: ...gine again For example if the conditions and parameter settings are given as follows 1 stop duration is 10 seconds crank attempt is 3 times The engine cranks for 10 seconds and then rest for 10 second...

Page 5: ...CT 2 input I2 51 CT 3 input I3 52 CT Common input Com 53 Sensor V output Sensor V 54 Sensor Common GND input Common 55 Oil pressure sensor input Oil Press 56 Oil temperature sensor input Oil Temp 57...

Page 6: ...6 2 Dimension...

Page 7: ...W KWH 6 P F 7 RPM 8 Engine parameter settings 9 Battery voltage 10 Exerciser 11 Water temperature 12 Oil pressure 13 1024 Event log 14 64 Error record B Remote access 1 Start stop and reset 2 Paramete...

Page 8: ...ion DC input 8 36 VDC Power consumption Max 24 W Voltage measurement 0 500VAC 0 2 Current measurement 0 5 A CT ratio 0 2 Frequency measurement 0 80 Hz 0 02 Charger or pickup voltage 5 V 70 V peak to p...

Page 9: ...fault 10 Description Set the duration of each crank 4 Crank attempts Setting 1 10 Default 3 Description Set total number of crank attempts 5 Escape up limit Setting 15 30 Hz Default 20 Description Whe...

Page 10: ...iggering engine shutdown failed alarm 5 Trip then shut Setting Disable Enable Default Enable Description When error occurred timer starts before shutdown the engine 6 Trip duration Setting 30 900 Seco...

Page 11: ...Description Set the hour meter in hours 4 Acc Hour 100 Setting 0 99 100 Default 0 Description Set the hour meter in 100 hours scale 4 Sensors Switches 1 H W T Detection Setting Disable Enable Default...

Page 12: ...tion Activates Input 0 function 3 Input 0 Name Setting 1 Emergency Stop 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling failure 9 Malfunc...

Page 13: ...ally close or normally open 11 In1 delay Setting 0 2 5 0 Seconds Default 2 0 Description When input1 activates timer starts before activating protection 12 Input 2 Detect Setting Disable Enable Defaul...

Page 14: ...ng 1 Warning 2 Alarm 3 Trip 4 Stop Default 4 Description Setup the action when input 3 activates 20 In3 Switch Type Setting NC NO Default Normal Open Description Setup Input 3 to normally close or nor...

Page 15: ...ressure switch 15 High water temperature switch 16 High AC voltage 17 Low AC voltage 18 Overload 19 Short circuit 20 Low battery voltage 21 High battery voltage 22 Input 0 activate 23 Input1activate 2...

Page 16: ...n the engine and display high frequency error if high frequency protection is enable 4 Hi Freq Delay Setting 1 9 Seconds Default 1 Description When high frequency occurres timer starts before activati...

Page 17: ...2 Batt Fault Alarm Setting Disable Enable Default Enable Description Activates battery error protections 3 L batt Set Point Setting 8 4 12 16 8 24 V Default 10 8 20 Description When battery voltage is...

Page 18: ...120 144 190 228 208 250 220 264 380 456 V Default 122 122 210 242 242 418 Description When AC voltage is above the setting the controller outputs trip signal 5 Hi ACV Delay Setting 0 5 5 Seconds Defa...

Page 19: ...ription Disconnect starter motor by Genset voltage 13 Esc ACV Setpoint Setting 44 100 48 108 76 172 84 188 88 198 152 342 V Default 72 72 124 124 132 228 Description Disconnect starter motor when AC V...

Page 20: ...tio 5 Overload Delay Setting 10 300 Second Default 40 Description When overload occurres timer starts before activating protection 6 Short Detect Setting Disable Enable Default Enable Description Acti...

Page 21: ...tion 1800 460 3 913 The R P M calculation formula is as below R P M Input pulse RPM numerator RPM denominator 1800 460 90 23 B If the engine revolution is 1500 and total count of fly wheel teeth in on...

Page 22: ...peed is enabled 8 Over speed delay Setting 1 10 Second Default 1 Description When over speed occurres timer starts before activating protection 12 Sensors 1 LFL Value Alarm Setting Disable Enable Defa...

Page 23: ...fault 45 Description Disconnect starter motor when oil pressure reaches setting 10 OP Sensor Brand Setting VDO 10 Bar KD 10 Bar YG 962 N 010 B2 KL 3967251 MHI 10 Bar DATCON 10 Bar SUSUKI 10 Bar VDO 5...

Page 24: ...p monthly exercise by date or week 3 Date set point Setting 1 31 date Default 28 Description Setup date of monthly exercise 4 Week set point Setting Sunday Monday Tuesday Wednesday Thursday Friday sat...

Page 25: ...ration between each service 15 OverLoad Protect 1 Over Load Detect Setting Disable Enable Description Activates over load detection 2 Overload protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Descripti...

Page 26: ...ess Setting 0 255 00H FFH Default FFH Description Multiple Genset networking via RS 485 requires individual address for each controller 4 Not in AUTO Mode Setting Disable Enable Description When GTR 2...

Page 27: ...iption Reset user password 3 Maintain Code Description Reset engineer password 4 Crank information Description a Total count Display total number of crank attempts b Fail count Display total number of...