
[10]
Default
:
0
Description
:
Duration of engine idle
2.
Engine Settings
1.
PreAdd Fuel Time
Setting
:
0.0~5.0(seconds)
Default
:
3
Description
:
Activates fuel pump before initiating crank procedure.
2.
Pre-Heat Time
Setting
:
0~20(Seconds)
Default
:
0
Description
:
Duration of Preheat before crank.
3.
Energied to Stop
Setting
:
1~30(seconds)
Default
:
10
Description
:
Output duration for stop solenoid to shut down the engine.
4.
Failed to stop
Setting
:
1~10(Seconds)
Default
:
2
Description
:
Time delay before triggering engine shutdown failed alarm.
5.
Trip then shut
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
When error occurred, timer starts before shutdown the engine
6.
Trip duration
Setting
:
30~900(Seconds)
Default
:
30
Description
:
When error occurred, controller outputs error signal, if error is not cleared
within setting, system initiates Genset shutdown.
7.
Cooling time
Setting
:
0~1250(Seconds)
Default
:
30
Description
:
Set engine cooling time for normal Genset shutdown. Engine cooling time is
disabled during malfunction shutdown
8.
Freq versus RPM
Setting
:
0~200
Default
:
30
Description: To conver RPM from
frequency, divide RPM by
frequency
(1800rpm/60HZ=30), 30 is the ratio for this setting.
Summary of Contents for GTR-620
Page 6: ...6 2 Dimension...