IP67 MDR for EtherNET/IP
Connect the MDR on the ports
2. Power wiring
•
Connect 24 VDC power supply to the
Power connectors
(to both UL and UB) of the HarshIO
module.
3. Communication wiring
•
Connect the first HarshIO module to the EtherNet/IP scanner with the appropriate Ethernet
network cable and the desired topology
4. Apply Power
Switch on the power supply module and observe the LEDs status indicator.
If the module is correctly wired, then the following LEDs status indicator should be:
LED
LED
indication
pattern
Module state
UL
Fixed green
Actuator voltage present
UB
Fixed green
Logic/Communications/sensor voltage present
Cx LEDs (Pin 2 & Pin4)
OFF
DI is not set / D0 is not energized
MDR LEDs
Fixed orange
MDR powered up, detected & stopped with counterclockwise
direction
Link ETHx
Blinking green
100 MB + No activity
NET (Network fault)
OFF
No IP address assigned
MOD (Module fault)
Blinking green
Module is started but no configuration received from the PLC
Note!
The result above is applicable if there is no EtherNET/IP connection between the
EtherNet/IP scanner and the HarshIO module.
Rockwell Studio 5000
We provide multiple materials for a better integration of the HarshIO module into Studio 5000 from
this link:
-
The technical note “Getting started with RS Studio5000” for better integration.
-
EDS file.