HarshIO 600
•
18
•
IP67 MDR for EtherNET/IP
Power Data
Module
4/5-pin power version
Power IN connector
Mini Change (7/8”), 4/5-pin, male, Maximum 8 A
Module & Input power (UB)
24 VDC, -20%/+25% (19.2 VDC / 30 VDC) protected against power crossing)
Warning, a voltage over 30 VDC may destroy the module
Operating current (UB)
90 mA (no I/O device connected)
Operating current (UL)
20 mA (no I/O device connected)
Max current consumption (UB)
8.2 Amps
Output Power (UL)
24 VDC, -10%/+10% (21.6 VDC / 26.4 VDC) for Itoh Denki
24 VDC, -10%/+10% (21.6 VDC / 28 VDC) for Interroll
(protected against power crossing)
Warning, a voltage over 30 VDC may destroy the module
Max current consumption (UL)
8.2 Amps
Galvanic isolation between UB & UL
500 V min
Electrical Signal Data
I/O Ports
I/O Ports
Max draw current per I/O ports
4 A
Sensor power pin
Pin 1 (L+ / Sensor power supply)
Sensors draw current from
UB
Sensors draw current (Pin 1)
200mA Nominal / 400mA Peak
Channels
Pin 2 (configured as)
Pin 4 (configured as)
Standard Digital Inputs
Number of Channel
4 channels max
4 channels max
Input type
PNP, compliant to IEC 61131-2 Type 3
PNP, compliant to IEC 61131-2 Type 3
On-state current
2.5 mA typ.
2.5 mA typ.
Off-state current
1 mA max.
1 mA max.
Input channel voltage (“1”)
10 V … 30 V
12 V … 30 V
Input channel voltage (“0”)
-
5 V … 5 V
-
5 V … 9 V
Input filter
1ms
1ms
Standard Digital Outputs
Outputs draw current from
UB
UB
Channels
4 channels max
4 channels max
Output voltage (min)
UB
– 1V
UB
– 1V
Output type
PNP, current sourcing
PNP, current sourcing
Output current
2 A per channel (4A peak)
2 A per channel (4A peak)
Maximum output current
8.0 A at 25°C: total for all outputs combined
8.0 A at 25°C: total for all outputs combined with
all sensor supply current
Short circuit current (typical)
up to 6.5 A
up to 6.5 A