Additional features of the device
How can I change the quantity of alarm notifications and time?
The temperature range of the sensor is from -40° C to +100° C. If the min. or max. value is exceeded, Compact
IIP+A send an alarm message to all the saved phone numbers. To SET the function use the following command:
SET TEMPERATURE <temp1> <temp2> #1513
Temp1 = lower limit
Temp2 = upper limit
The value of "Temp2" must be higher than "Temp1"
Example:
SET TEMPERATURE -5 35 #1513
By temperature lower than -5° C or higher than +35° C triggers the Compact an alarm. The adjustable range is from -
40 to 100.
If it is SET as "Temp1" = -40, turns off the lower limit
If it is SET as "Temp2" = 100, turns off the upper limit
If the value of "Temp1" is higher than "Temp2, send the device a message about this error.
Delete the SET limits
To delete the SET limits, use the command:
TEMPERATURE RESET #1513
Check SETtings
To check the existing SETtings, use the command:
TEST TEMPERATURE #1513