This product is non-dimmable.
This product should be dismantled for disposal when it reaches the end of its life. Please see website for
dismantling instructions.
This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities
for where facilities exist.
The batteries in this luminaire are Lithium Ion and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 5 years (excluding battery) from date of purchase. Failure to install this product
in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the
batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned
to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for
any installation costs associated with the replacement product. Your statutory rights are not affected. ML
Accessories reserve the right to alter product specification without prior notice.
TEST RECORD
Recommended routine test procedure in accordance with BS5266:
•
Daily check – check status of bi-colour LED indicator
•
Monthly functional test – the luminaire will perform this function without any action from the user.
Alternatively, simulate a mains supply failure for approx. 30 seconds by operation of key switch, switching
off circuit breaker or using test button. Ensure normal supply is restored after test and check status of bi-
colour LED indicator
•
3-hour duration test – the luminaire will perform this function without any action from the user. Alternatively,
simulate a mains supply failure for 3-hour continuous test by operation of key switch, or switching off circuit
breaker. Ensure normal supply is restored after test and check status of bi-colour LED indicator
•
If the luminaire fails any of the above tests, please contact a qualified electrician. Results should be
recorded, even when obtained via the self-test function. See below for test record sheet
230V 50Hz, IP20, Class 1, Non-Dim, indoor only, Ta -5~50
DCAPR22_V1