Chapter Two: Installation
Connectors
35
Bendix Connectors
The 870/872 transducer is available with a Bendix connector attached to the flying lead at the end
of the 9” cable (refer to Figure 10).
Side View
End View
9" Braided Shielded Cable
Bendix Connector
Figure 10: Bendix Connector
Warning
To prevent possible sparking, do not disconnect the Bendix
connector while the circuit is live unless the area is known to
be non-hazardous. There is a warning label on the cable (see
Figure 15, page 41) for all units with a Bendix connector.
Table 10 lists the pinout for the Bendix 4 pin PTO, male connector (Model Code D).
Bendix Connector Pinout (Model Code D)
Pin
Voltage Signal
Current Signal
A
+ Power Input
4 to 20 mA positive excitation
B
Pressure Output
Do Not Use
C
Pressure Return
Do Not Use
D
Power Return
4 to 20 mA negative excitation
Table 10: Bendix Connector Pinout (Model Code D)
Table 11 lists the pinout for the configuration of the Bendix 4 pin PTO, male connector (Model
Code H). This configuration is only available with the 4 to 20 mA output unit.
Bendix Connector Pinout (Model Code H)*
Pin
Signal
A
4 to 20 mA positive excitation
B
Jumpered to pin D
C
Reserved
D
4 to 20 mA negative excitation
* This configuration is only available with the 4 to 20 mA output
unit.
Summary of Contents for Micro-Baratron 870B
Page 3: ...123655 P1 Rev B 06 01 MKS Type 870B 872B Micro Baratron Absolute Pressure Transducer...
Page 8: ......
Page 10: ......
Page 28: ......
Page 52: ...Labels Chapter Three Overview 42 This page intentionally left blank...
Page 66: ...Model Code Appendix B Model Code Explanation 56 This page intentionally left blank...