How To Select the Digital Input Functions
Chapter Six: Remote Digital Logic Control
114
Digital Input Priorities
Digital inputs are scanned and selected in a prioritized manner, enabling a higher priority request
to override a lower one. The order of priority is shown in Table 18.
Priority of Digital Inputs
Order of Priority
I/O Pin No.
Digital Input Function
1
6
Analog set point
(pressure or position)
2
10
Control range of analog set point
Note:
Below this point, if any of the digital inputs are held low, lower priority
signals are blocked; that is, they are not recognized until the higher priority
signal is released.
3
25
Remote zero
4
5
No function
5
8
Close valve
6
27
Open valve*
7
26
Stop valve*
8
11
Select analog set point
9
16
Select set point A
10
15
Select set point B
11
14
Select set point C
12
13
Select set point D
13
12
Select set point E
* Activating both the
open
and
close
commands simultaneously causes the
valve to
stop
.
Table 18: Priority of Digital Inputs
The order of priority of digital inputs is based on the analog set point line (pin 11) being tied low
to continuously select it, thus blocking set points A through E, except to use their gains.
Summary of Contents for 651D Series
Page 1: ...118965 P1 Preliminary 5 02 MKS Type 651D Pressure Controller...
Page 8: ......
Page 10: ......
Page 12: ......
Page 20: ...Customer Support Chapter One General Information 8 This page intentionally left blank...
Page 50: ...Labels Chapter Three Overview 38 This page intentionally left blank...
Page 78: ......
Page 149: ...Appendix C Initial Settings 137 This page intentionally left blank...
Page 150: ......
Page 158: ...Appendix E RS 232 Message Summary 146 This page intentionally left blank...