5 DeviceNet Operation
Series 275 Convectron Module with DeviceNet
Instruction Manual - 275502
29
Table 5-5
Connection Object - Polled I/O Connection
Service Class Instance Attribute Master data
Device data
Data type
Description
Type
0E
hex
5
2
1
None
3
USINT
Get state of the object, range 0–5
Open
0E
hex
5
2
2
None
1
USINT
Get instance type, I/O
Open
0E
hex
5
2
3
None
82
hex
BYTE
Get transport class trigger
Open
0E
hex
5
2
4
None
FF 03
UINT
Get produced connection ID
Open
0E
hex
5
2
5
None
FD 05
UINT
Get consumed connection ID
Open
0E
hex
5
2
6
None
01
hex
BYTE
Get initial communication characteristics
Open
0E
hex
5
2
7
None
05 00
UINT
Get produced connection size
Open
0E
hex
5
2
8
None
01 00
UINT
Get consumed connection size
Open
0E
hex
5
2
9
None
00 00
UINT
Get expected packet rate, range 0–65535
Open
10
hex
5
2
9
00 00
Success
UINT
Set expected packet rate
Open
0E
hex
5
2
0C
hex
None
0
USINT
Get watchdog timeout action
Open
0E
hex
5
2
0D
hex
None
06 00
UINT
Get produced connection path length
Open
10
hex
5
2
0D
hex
None
1
EPATH
Set produced connection path length
Open
0E
hex
5
2
0E
hex
None
01
EPATH
Get produced connection path
Open
0E
hex
5
2
0F
hex
None
06 00
UINT
Get consumed connection path length
Open
0E
hex
5
2
10
hex
None
00
EPATH
Get consumed connection path
Open
Parameter Object
There are two instances of the Parameter Object. Instance #1 manages the offset (vacuum)
calibration. This two-byte value represents the desired output. Performing the Get_Attribute_Single
service initiates the calibration sequence. Instance #2 manages the gain (atmosphere) calibration.
This two-byte value represents the desired output. Performing the Get_Attribute_Single service
initiates the calibration sequence.
Table 5-6
Explicit Message Summary - Parameter Object
Service Class Instance Attribute Master data
Device data
Data type
Description
Type
0E
hex
0F
1
1
None
00 00
UINT
Indicate data used with last "set"
Vendor specific
10
hex
0F
1
1
00 00
None
UINT
Set vacuum reading to Zero - transducer
must be measuring vacuum
Vendor specific
0E
hex
0F
2
1
None
60 E0
UINT
Indicate data used with last "set"
Vendor specific
10
hex
0F
2
1
60 E0
None
UINT
Set Atmosphere reading to 760 Torr -
transducer must be measuring
Atmosphere
(Gold Sensor)
Vendor specific
10
hex
0F
2
1
F7 E0
None
UINT
Set Atmosphere reading to 760 Torr -
transducer must be measuring
Atmosphere
(Platinum Sensor)
Vendor specific
Summary of Contents for 275420-1-GQ-T-00011
Page 2: ......
Page 26: ...4 Operation 26 Series 275 Convectron Module with DeviceNet Instruction Manual 275502 Notes...
Page 31: ...5 DeviceNet Operation Series 275 Convectron Module with DeviceNet Instruction Manual 275502 31...
Page 32: ...5 DeviceNet Operation 32 Series 275 Convectron Module with DeviceNet Instruction Manual 275502...
Page 50: ......
Page 51: ......