'11 • SCM-SM-110
2)
Air flow direction is controlled according to the indoor temperature and setting temperature.
a)
When D auto operation starts
b)
When Indoor temp. – Setting temp. is
<
=
ºC during cooling and when Setting temp. – Indoor temp. is
<
=
ºC during
heating, the system switches to the following air flow direction control. After the louver swings left and right sym-
metrically for cycles, control is switched to the control in c).
c)
After the flap swings for cycles, control is switched to the control in d).
d)
For minutes, the following air flow direction control is carried out.
e)
After minutes have passed, the air flow direction is determined according to the indoor temperature and setting
temperature.
(b)
During DRY Operation (including auto DRY operation)
Flap
Louver
Cooling
Up/down Swing
Heating
Wide (fixed)
Center (fixed)
Flap
Louver
Cooling
Heating
Left/right Swing
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Flap
Louver
Cooling
Up/down Swing
Heating
Center (Fixed)
Wide (Fixed)
Flap
Louver
Cooling
Heating
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Operation mode
Indoor temp. – Setting temp. 2°C
Setting temp. – Indoor temp. 2°C
At heating
At cooling
Air flow direction contorol
2°C < Setting temp. – Indoor temp. 5°C
2°C < Indoor temp. – Setting temp. 5°C
Indoor temp. – Setting temp. > 5°C
Setting temp. – Indoor temp. > 5°C
The control in d) continues.
Control returns to the control in b).
Control returns to the control in a).
The control in d) continues.
Control returns to the control in b).
Control returns to the control in a).
<
=
<
=
<
=
<
=
Wide (Fixed)
Flap
Air flow selection
Louver
According to DRY operation.
Horizontal blowing (Fixed)
(b) Sleep timer operation
Pressing the SLEEP button causes the temperature to be controlled with respect to the set temperature.
(11) Timer operation
(a) Comfortable timer setting (ON timer)
(c) OFF timer operation
The OFF timer can be set at a specific time (in 10-minute units) within a 24-hour period.
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode
operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value
of minutes and the relationship between the indoor temperature at the setting time (temperature of room temperature sensor)
and the setting temperature.