'11 • SCM-SM-110
2) Selection of indoor fan speed
If it enters the frost prevention control during cooling operation (excluding dehumidifying), the indoor unit fan speed is
switched.
(a) In cases of FDEN
i) When the indoor unit return air temperature (detected with ThI-A) is 23°C or lower, this control is invalidated
and, as 2 hours elapse after starting the frost prevention control, it is terminated.
ii) If it is detected again within 15 minutes from the start of frost prevention control, the indoor fan speed is raised
by 1 tap to increase the indoor unit fan speed. If it is detected within further 15 minutes, the indoor unit fan
speed is raised by 1 tap more.
Note (1) Indoor unit fan speed can be increased by up to 2 taps.
iii) “ FAN SPEED SW VALID/INVALID” of this control is selectable with the function setting of remote
controller.
b) In the case of FDTC and FDUM
i) When the indoor return air detection temperature (detected with ThI-A) is 23°C or higher and the indoor heat
exchanger temperature (detected with ThI-R) detects the compressor frequency drop start temperature A°C+1°C,
of indoor unit fan speed is increased by 20rpm.
ii) If the phenomenon of i) above is detected again after the acceleration of indoor unit fan, indoor unit fan speed
is increased further by 20rpm.
Note (1) Indoor unit fan speed can be increased by up to 2 taps.
• Compressor frequency drop start temperature
Symbol
Item
A
Temperature - Low (Factory default)
1.0
Temperature - High
2.5
Note (1) Frost prevention temperature setting can be selected with the indoor unit function setting of the wired remote controller.
(p) Heating overload protection
1) If the indoor heat exchanger temperature (detected with ThI-R) at 63°C or higher is detected for 2 seconds continuously,
the compressor stops. When the compressor is restarted after a 3-minute delay, if a temperature at 63°C or higher is
detected for 2 seconds continuously within 60 minutes after initial detection and if this is detected 5 times consecutively,
the compressor stops with the anomalous stop (E8). Anomalous stop occurs also when the indoor heat exchanger
temperature at 63°C or higher is detected for 6 minutes continuously.
56
63
Indoor heat exchanger temperature (°C)
Compressor ON
Compressor OFF
2) Indoor unit fan speed selection
If, after second detection of heating overload protection up to fourth, the indoor fan is set at Me and Lo taps when the
compressor is turned ON, the indoor fan speed is increased by 1 tap.
(q) Anomalous fan motor [In case of FDTC and FDUM]
) After starting the fan motor, if the fan motor speed is 00rpm or less is detected for 0 seconds continuously and times
within 0 minutes, then fan motor stops with the anomalous stop (E).
) If the fan motor fails to reach at -0 rpm less than the required speed, it stops with the anomalous stop (E0).
(r) Plural unit control – Control of 16 units group by one remote controller
)
Function
One remote controller switch can control a group of multiple number of unit (Max. indoor units). “Operation mode”
which is set by the remote controller switch can operate or stop all units in the group one after another in the order of unit
No.
()
. Thermostat and protective function of each unit function independently.
Note () Unit No. is set by SW on the indoor unit control PCB. Unit No. setting by SW is necessary for the indoor unit only.