background image

11

6. Electrical work

6.3. Wiring transmission cables

1

 

Types of control cables

1.  Wiring transmission cables

•  Types of transmission cables: Shielding wire CVVS or CPEVS or MVVS

•  Cable diameter: More than 1.25 mm

2

 

•  Maximum wiring length: Within 200 m
2.  M-NET Remote control cables

Kind of remote control cable Shielding wire (2-core) CVVS, CPEVS or MVVS.

Cable diameter 

0.5 to 1.25 mm

[AWG 20 to AWG 16]*

Remarks 

When 10 m

 

[32 ft] is exceeded, use cable with 

the same specifications as transmission line 

wiring.

* Connected with simple remote controller.

M1

S

M2

B

A

C

M1

S

M2

TB3

TB1

TB7

D

L1 L2 GR

6.2. Control box and connecting position of wiring

   (Fig. 6-1)

1.  Connect the branch box transmission line to transmission terminal block (TB3), 

or connect the wiring between outdoor units or the wiring with the centralized 

control system to the centralized control terminal block (TB7).

 

When using shielded wiring, connect shield ground of the branch box transmis-

sion line to the screw (

C

 or 

D

) and connect shield ground of the line between 

outdoor units and the central control system transmission line to the shield (S) 

terminal of the centralized control terminal block (TB7) shield (S) terminal. In 

addition, in the case of outdoor units whose power supply connector CN41 has 

been replaced by CN40, the shield terminal (S) of terminal block (TB7) of the 

centralized control system should also be connected to the screw (

C

 or 

D

)

 

using 

attached lead wire.

2.  Conduit mounting plates are being provided. Pass the power supply and 

transmission wires through the appropriate knock-out holes, then remove the 

knock-out piece from the bottom of the terminal box and connect the wires.

3.  Fix power source wiring to terminal box by using buffer bushing for tensile force 

(PG connection or the like).

 Caution:

Never connect the transmission line for the branch box or the central control 

system transmission line to this terminal bed (TB1B). If the transmission 

lines are connected, the indoor unit terminal block, branch box terminal 

block or centralized control terminal block could be damaged.

Fig. 6-1

3.  MA Remote control cables

Kind of remote control cable

Sheathed 2-core cable (unshielded) CVV

Cable diameter

0.3 to 1.25 mm

(0.75 to 1.25 mm

2

)*

Remarks 

Within 200 m

*  Connected with simple remote controller.

2

 

Wiring examples

•  Controller name, symbol and allowable number of controllers.

Name

Symbol

Allowable number of controllers

Outdoor unit controller

OC

Indoor unit controller

IC

PUMY-P36NKMU1 1 to 7 units per 1 OC
PUMY-P48NKMU1 1 to 10 units per 1 OC

Remote controller

RC

MA

Maximum of 2 per group

CONDUIT PLATE: 
accessory

ø24 knock-out hole
(For transmission wires)

ø37 knock-out hole
(For power supply wires)

 CONDUIT WASHER: 

accessory

Example of a group operation system with multiple outdoor units (Shielding wires and address setting are neces

-

sary.)

<Examples of Transmission Cable Wiring>

 

M-NET Remote Controller (Fig. 6-2)

 

MA Remote Controller (Fig. 6-3)

<Wiring Method and Address Settings>

a.  Always use shielded wire when making connections between the outdoor unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.

b.  Use feed wiring to connect terminals M1 and M2 and the ground terminal on the transmission cable terminal block (TB3) of each outdoor unit (OC) to terminals M1, M2 

and terminal S on the transmission cable block of the indoor unit (IC).

c.  Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the 

terminal block on the remote controller (RC).

d.  Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the outdoor unit (OC).

e.  The jumper connector CN41 on the control panel does not change.

f.  Connect the terminal S on the terminal block for central control  for the power supply unit  to the ground terminal (

) in the electrical component box.

g.  Set the address setting switch as follows.

Unit

Range

Setting Method

IC (Main)

01 to 50

Use the most recent address within the same group of  indoor units

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be in 

sequence with the IC (Main)

Outdoor Unit

51 to 100

Use the most recent address of all the indoor units plus 50

*  The address automatically becomes “100” if it is set as “01 - 50”.

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

MA R/C

Unnecessary address setting (Necessary main/sub setting)

h.  The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

<Permissible Lengths>

1

 

M-NET Remote controller

•    Max length via outdoor units: L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

3

+L

5

 and L

1

+L

2

+L

6

+L

7

   500 m [1640 ft] (1.25 mm

2

 [AWG16] or more)

•  Max transmission cable length: L

and L

3

+L

4

 and L

3

+L

5

 and L

2

+L

6

 and L

7

   200 m [656 ft] (1.25 mm

2

 [AWG16] or more)

•  Remote controller cable length: 

1

2

2

 +

3

4

   10 m [33 ft] (0.5 to 1.25 mm

2

 [AWG20 to AWG16])

If the length exceeds 10 m [33 ft], use a 1.25 mm

2

 [AWG16] shielded wire.  The length of this section (L

8

) should be included in the 

calculation of the maximum length and overall length.

2

 

MA Remote controller

•    Max length via outdoor unit (M-NET cable): L

1

+L

2

+L

3

+L

4

 and L

1

+L

2

+L

6

+L

7

   500 m [1640 ft] (1.25 mm

2

 [AWG16] or more)

•  Max transmission cable length (M-NET cable): L

and L

3

+L

4

 and L

2

+L

6

 and L

7

   200 m [656 ft] (1.25 mm

2

 [AWG16]

 

or more)

•  Remote controller cable length: m

1

 and m

1

+m

2

 +m

3

 and m

1

+m

2

+m

3

+m

4

   200 m [656 ft] (0.3 to 1.25 mm

2

 [AWG20 to AWG16])

C

  Screw on the electrical component box

D

  Screw on the electrical component box

A

  Power source

B

  Transmission line

RG79F079H01_EN.indd   11

2/24/2016   2:57:23 PM

Summary of Contents for PUMY-P36NKMU1

Page 1: ...ce climatiseur pour viter tout accident et vous assurer d une utilisation correcte MANUAL DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la...

Page 2: ...nit use only the specified refrigerant R410A to change the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant t...

Page 3: ...nd flare the flared sections again Do not use thin pipes Refer to page 6 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave e...

Page 4: ...f connected units Outdoor unit model name The capacity of outdoor unit Number of units that can be connected Capacity range of connected units PUMY P36NKMU1 36kBtu h 1 7 units 18 46 8 kBtu h PUMY P48N...

Page 5: ...10 Do not install the optional air outlet guides for upward airflow 2 5 3 When installing multiple outdoor units Leave 1 25 mm space or more between the units 1 Obstacles at rear Fig 2 11 2 Obstacles...

Page 6: ...ed below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil ap plied to the flared sections Use C1220 copper phosphorus for...

Page 7: ...16 2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation 3 Refrigerant pipe bending radius must be 4 100 mm or more Caution Be sure to use the insulation of specified thickness E...

Page 8: ...mm 4 inch to 150 mm 6 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1Pipes must be connected starting from the indoor unit Flare nuts mu...

Page 9: ...tectively wrapped The pipes can be protectively wrapped up to a diameter of 90 mm 3 9 16 before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the p...

Page 10: ...ransmission line Other Terminal block TB7 for centralized control Erroneous connection does not allow the system to operate 8 In case to connect with the upper class controller or to conduct group ope...

Page 11: ...units Shielding wires and address setting are neces sary Examples of Transmission Cable Wiring M NET Remote Controller Fig 6 2 MA Remote Controller Fig 6 3 Wiring Method and Address Settings a Always...

Page 12: ...current protec tor device Main Cable 2 Ground Outdoor Unit P36 48 208 230 VAC 60 Hz 8 4 AWG8 8 4 AWG8 40 A 40 A 30 mA 0 1 sec or less 31 A 44 A Indoor Unit 208 230 VAC 60 Hz Refer to installation man...

Page 13: ...ower cord size should be 1 rank thicker consideration of voltage drops Make sure the power supply voltage does not drop more than 10 4 Specific wiring requirements should adhere to the wiring regulati...

Page 14: ...insulation resistance drops due to accumulation of refrigerant in the compressor The resistance will rise above 1 M after the compressor is warmed up for 12 hours The time necessary to warm up the com...

Page 15: ...demand control are selected by switching the DIP switch 9 2 on outdoor controller board It is possible to set it to the following power consumption compared with ratings by setting SW1 2 Outdoor contr...

Page 16: ...roduire Lors de l installation du d placement ou de l entretien de l appareil ext rieur n utilisez que le r frig rant sp cifi R410A pour remplir les tuyaux de r frig rant Ne pas le m langer avec un au...

Page 17: ...r les crous vas s existants et vaser de nouveau les sections vas es Ne pas utiliser de tuyaux fins Se reporter la page 20 Stocker l int rieur les tuyaux utiliser pendant l installation et couvrir les...

Page 18: ...plage de capacit s des appa reils raccord s Nom de mod le appareil ext rieur Capacit de l appareil ext rieur Nombre d appa reils pouvant tre raccord s Plage de capaci t s des appareils raccord s PUMY...

Page 19: ...les guidages de sortie d air en option pour un d bit d air vers le haut 2 5 3 Lors de l installation de plusieurs appareils ext rieurs Espacer les appareils de 1 25 mm minimum 1 Obstacles l arri re Fi...

Page 20: ...nt R410A Se reporter la page 17 pour les consignes non reprises ci dessous concernant l utilisation de climatiseurs avec un r frig rant R410A Appliquer une petite quantit d huile ester ther ou alkylbe...

Page 21: ...g rant sont isol s pour emp cher la formation de condensation 3 Le rayon de pliage du tuyau de r frig rant doit tre de 4 pouce 100 mm minimum Pr caution Veiller utiliser l isolation de l paisseur indi...

Page 22: ...courbure Un rayon de courbure de 100 mm 4 pouces 150 mm 6 pouce est suffisant V rifier que les tuyaux ne touchent pas le compresseur Des vibrations ou des bruits anormaux pourraient se produire 1Racc...

Page 23: ...sont entour s d une couche de protection Les tuyaux peuvent tre entour s apr s ou avant avoir t raccord s d une couche de protection allant jusqu 90 3 9 16 D couper la rondelle d fon able du cache tu...

Page 24: ...appareil ext rieur Ligne de transmission raccorder l appareil int rieur Bloc terminal TB3 pour la ligne de transmission Autres Bloc terminal TB7 pour une commande centralis e Une mauvaise connexion e...

Page 25: ...L1 L2 GR RONDELLE POUR GAINE LECTRIQUE accessoire Exemple de syst me de fonctionnement reli la terre avec plusieurs appareils ext rieurs Il est n cessaire d uti liser des c bles blind s et de d finir...

Page 26: ...pouce minimum entre les contacts de chaque p le 2 Utiliser des c bles lectriques en cuivre Utiliser des c bles lectriques correspondant une tension de 300 V Courant total d exploitation de l appareil...

Page 27: ...temp rature ambiante rayons solaires directs eau pluviale etc lors du c blage et du raccordement des appa reils 3 Les dimensions des c bles repr sentent les dimensions minimales pour le c blage de con...

Page 28: ...frig rant ne peut pas s effectuer Attendre 3 minutes apr s l arr t du compresseur avant de r activer les commutateurs SW3 1 et SW3 2 6 Fermer compl tement le robinet d arr t du gaz lorsque le manom t...

Page 29: ...ux et du contr le de la demande se fait par commutation du commutateur DIP 9 2 du panneau de commande ext rieur Les consommations lectriques suivantes par rapport aux valeurs nominales peuvent tre d f...

Page 30: ...el refrigerante indicado R410A para cargar los tubos del refrigerante No lo mezcle con otro tipo de refrigerante y vac e completamente de aire los tubos Si el aire se mezcla con el refrigerante podr a...

Page 31: ...gerante R22 Sustituya las tuercas de abocardado existentes y vuelva a abocardar las seccio nes abocardadas No use tuber as de poco grosor Consulte la p gina 34 Almacene las tuber as que se deban insta...

Page 32: ...ctadas Nombre del modelo de unidad exterior La capacidad de la unidad exterior N mero de unida des que pueden conectarse Intervalo de capaci dades de las unida des conectadas PUMY P36NKMU1 36kBtu h 1...

Page 33: ...aire opcionales para corriente de aire hacia arriba 2 5 3 Cuando instale varias unidades exteriores Deje un espacio de 1 25 mm o m s entre las unidades 1 Obst culos en la parte trasera Fig 2 11 2 Obs...

Page 34: ...Consulte la p gina 31 para las precauciones a tomar en equipos que utilicen el refrigerante R410A y que no se encuentren a continuaci n Utilice aceite de ster de ter o alquilobenceno en peque as cant...

Page 35: ...8 5 16 2 Aseg rese de que los 2 tubos de refrigerante est n aislados para evitar la con densaci n 3 El radio m nimo de curvatura debe ser de 4 100 mm o m s Cuidado Aseg rese de utilizar el aislamient...

Page 36: ...erlos Un radio de curvatura de 100 mm 4 pulg a 150 mm 6 pulg resultar suficiente Aseg rese de que las tuber as no tocan el compresor Podr a producir ruidos o vibraciones extra as 1 Las tuber as se deb...

Page 37: ...ial aislante no se impregnen de agua Las tuber as de refrigerante est n envueltas con una protecci n Los tubos se pueden envolver para su protecci n hasta un di metro de 90 mm 3 9 16 antes de conectar...

Page 38: ...esultante dar lugar a funciones err neas 7 nicamente la l nea de transmisi n especificada deber a ser conectada al bloque de terminal para la transmisi n de la unidad exterior La l nea de transmisi n...

Page 39: ...ornillar en la caja de componentes el ctricos A Fuente de alimentaci n B L nea de transmisi n Ejemplo de un sistema de funcionamiento en tierra con varias unidades exteriores Se requiere cable blindad...

Page 40: ...corriente 3 20 20 20 F0 30 A o menos 2 5 5 10 5 5 10 5 3 10 30 A sensibilidad a la corriente 3 30 30 30 Aplicar a IEC61000 3 3 aproximadamente m x impedancia permitida en el sistema 1 El interruptor d...

Page 41: ...cales 5 Los cables de alimentaci n principal de los componentes de aparatos destinados al uso en la intemperie no deben ser m s livianos que el cable flexible con revestimiento de policioropreno dise...

Page 42: ...3 minutos despu s de que el compresor se haya parado la operaci n de recuperaci n del refrigerante no se puede realizar Espere al menos a que el compresor haya estado parado durante 3 minutos y vuelva...

Page 43: ...comparado con los ndices ajustando SW1 2 Placa del controlador exterior DIP SW9 2 SW1 SW2 Funci n Modo silencioso OFF ON Funcionamiento en modo silencioso Control de demanda ON OFF OFF 100 Normal ON...

Page 44: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment RG79F079H01 Printed in Japan HEAD OFFICE T...

Reviews: