4. Installing the refrigerant piping

4.3. Connecting pipes (Fig. 4-2) (Fig. 4-3)

•  Conduct sufficient anti-condensation and insulation work to prevent water drip-

ping from the refrigerant piping. (liquid pipe/gas pipe)

•  Increase insulation depending on the environment where the refrigerant piping is 

installed, or condensation may occur on the surface of the insulation material. 

(Insulation material Heat-resistant temperature: 120 °C, 248 °F, Thickness: 

15 mm, 5/8 inch or more)

*  When the refrigerant piping is used in locations subject to high tempera-

ture and humidity such as in the attic, further addition of insulation may be 

required.

•  To insulate the refrigerant piping, apply heat-resistant polyethylene foam between 

the indoor unit and insulation material as well as to the net between the insulation 

material filling all gaps. 

(Condensation forming on the piping may result in condensation in the room or 

burns when contacting the piping.)

•   The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-

lation materials (specific gravity of 0.03, thickness of 9 mm (3/8 inch) or more).

[Fig. 4-3]

•   Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening 

flare nut.

 A

•  Use 2 wrenches to tighten piping connections. 

B

•   Use  leak  detector  or  soapy  water  to  check  for  gas  leaks  after  connections  are 

completed.

•  Apply refrigerating machine oil over the entire flare seat surface. 

C

•  Use the flare nuts as follows. 

D

•   When bending the pipes, be careful not to break them. Bend radius of 100 mm 

(4 inch) to 150 mm (6 inch) are sufficient.

•   Make sure the pipes do not contact the compressor. Abnormal noise or vibration 

may result.

1

 Pipes must be connected starting from the indoor unit.

Flare nuts must be tightened with a torque wrench.

2

  Flare the liquid pipes and gas pipes and apply a thin layer of refrigeration oil (Ap-

plied on site).

•   When usual pipe sealing is used, refer to Table 2 for flaring of R410A refrigerant 

pipes.

The size adjustment gauge can be used to confirm A measurements.

 Warning:

When installing the unit, securely connect the refrigerant pipes before starting 

the compressor.

 Caution:

•  Be sure to wrap insulation around the piping. Direct contact with the bare 

piping may result in burns or frostbite.

Table 2 (Fig. 4-4

mm (inch)

Copper pipe O.D. 

 A 

 Flare tool for R410A  

 Flare tool for R22·R407C  

Clutch type  

ø6.35 (1/4)  

0 - 0.5 (0 - 1/64) 

1.0 - 1.5 (3/64 - 1/16)

ø9.52 (3/8)  

0 - 0.5 (0 - 1/64)

1.0 - 1.5 (3/64 - 1/16) 

ø12.7 (1/2)  

0 - 0.5 (0 - 1/64)

1.0 - 1.5 (3/64 - 1/16) 

ø15.88 (5/8)  

0 - 0.5 (0 - 1/64)

1.0 - 1.5 (3/64 - 1/16)

A

 (Fig. 4-3)

Copper pipe O.D.

(mm) (inch)

Flare dimensions

øA dimensions (mm) (inch)

ø6.35 (1/4)  

8.7 - 9.1 (5/16 - 3/8)

ø9.52 (3/8)  

12.8 - 13.2 (1/2 - 33/64)

ø12.7 (1/2)  

16.2 - 16.6 (41/64 - 21/32) 

ø15.88 (5/8)  

19.3 - 19.7 (49/64 - 25/32)

Copper pipe O.D.

 (mm) (inch)

Flare nut O.D.

(mm) (inch)

Tightening torque

(N·m)* (ft·lbs)

ø6.35 (1/4) 

17 (43/64)

14 - 18 (10 - 13)

ø6.35 (1/4) 

22 (7/8) 

34 - 42 (25 - 30)

ø9.52 (3/8) 

22 (7/8) 

34 - 42 (25 - 30)

ø9.52 (3/8) 

26 (1-3/64)

49 - 61 (35 - 44)

ø12.7 (1/2) 

26 (1-3/64)

49 - 61 (35 - 44)

ø12.7 (1/2) 

29 (1-9/64)

68 - 82 (49 - 59)

ø15.88 (5/8) 

29 (1-9/64)

68 - 82 (49 - 59)

ø15.88 (5/8) 

36 (1-27/64)

100 - 120 (71 - 87)

* 1 N·m 10 kgf·cm

A

B

C

D

A

 Liquid pipe

B

 Gas pipe

C

 Insulation

D

 Taping

Fig. 4-2

Fig. 4-3

A

 Flare cutting dimensions

B

 Flare nut tightening torque

90° ± 0.5°

R1/64" to R1/32"

øA

45°± 2°

Fig. 4-4

A

 Die

B

 Copper pipe

A

RG79F079H01_EN.indd   8

2/24/2016   2:57:20 PM

Summary of Contents for PUMY-P36NKMU1

Page 1: ...ce climatiseur pour viter tout accident et vous assurer d une utilisation correcte MANUAL DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la...

Page 2: ...nit use only the specified refrigerant R410A to change the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant t...

Page 3: ...nd flare the flared sections again Do not use thin pipes Refer to page 6 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave e...

Page 4: ...f connected units Outdoor unit model name The capacity of outdoor unit Number of units that can be connected Capacity range of connected units PUMY P36NKMU1 36kBtu h 1 7 units 18 46 8 kBtu h PUMY P48N...

Page 5: ...10 Do not install the optional air outlet guides for upward airflow 2 5 3 When installing multiple outdoor units Leave 1 25 mm space or more between the units 1 Obstacles at rear Fig 2 11 2 Obstacles...

Page 6: ...ed below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil ap plied to the flared sections Use C1220 copper phosphorus for...

Page 7: ...16 2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation 3 Refrigerant pipe bending radius must be 4 100 mm or more Caution Be sure to use the insulation of specified thickness E...

Page 8: ...mm 4 inch to 150 mm 6 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1Pipes must be connected starting from the indoor unit Flare nuts mu...

Page 9: ...tectively wrapped The pipes can be protectively wrapped up to a diameter of 90 mm 3 9 16 before or after connecting the pipes Cut out the knockout in the pipe cover following the groove and wrap the p...

Page 10: ...ransmission line Other Terminal block TB7 for centralized control Erroneous connection does not allow the system to operate 8 In case to connect with the upper class controller or to conduct group ope...

Page 11: ...units Shielding wires and address setting are neces sary Examples of Transmission Cable Wiring M NET Remote Controller Fig 6 2 MA Remote Controller Fig 6 3 Wiring Method and Address Settings a Always...

Page 12: ...current protec tor device Main Cable 2 Ground Outdoor Unit P36 48 208 230 VAC 60 Hz 8 4 AWG8 8 4 AWG8 40 A 40 A 30 mA 0 1 sec or less 31 A 44 A Indoor Unit 208 230 VAC 60 Hz Refer to installation man...

Page 13: ...ower cord size should be 1 rank thicker consideration of voltage drops Make sure the power supply voltage does not drop more than 10 4 Specific wiring requirements should adhere to the wiring regulati...

Page 14: ...insulation resistance drops due to accumulation of refrigerant in the compressor The resistance will rise above 1 M after the compressor is warmed up for 12 hours The time necessary to warm up the com...

Page 15: ...demand control are selected by switching the DIP switch 9 2 on outdoor controller board It is possible to set it to the following power consumption compared with ratings by setting SW1 2 Outdoor contr...

Page 16: ...roduire Lors de l installation du d placement ou de l entretien de l appareil ext rieur n utilisez que le r frig rant sp cifi R410A pour remplir les tuyaux de r frig rant Ne pas le m langer avec un au...

Page 17: ...r les crous vas s existants et vaser de nouveau les sections vas es Ne pas utiliser de tuyaux fins Se reporter la page 20 Stocker l int rieur les tuyaux utiliser pendant l installation et couvrir les...

Page 18: ...plage de capacit s des appa reils raccord s Nom de mod le appareil ext rieur Capacit de l appareil ext rieur Nombre d appa reils pouvant tre raccord s Plage de capaci t s des appareils raccord s PUMY...

Page 19: ...les guidages de sortie d air en option pour un d bit d air vers le haut 2 5 3 Lors de l installation de plusieurs appareils ext rieurs Espacer les appareils de 1 25 mm minimum 1 Obstacles l arri re Fi...

Page 20: ...nt R410A Se reporter la page 17 pour les consignes non reprises ci dessous concernant l utilisation de climatiseurs avec un r frig rant R410A Appliquer une petite quantit d huile ester ther ou alkylbe...

Page 21: ...g rant sont isol s pour emp cher la formation de condensation 3 Le rayon de pliage du tuyau de r frig rant doit tre de 4 pouce 100 mm minimum Pr caution Veiller utiliser l isolation de l paisseur indi...

Page 22: ...courbure Un rayon de courbure de 100 mm 4 pouces 150 mm 6 pouce est suffisant V rifier que les tuyaux ne touchent pas le compresseur Des vibrations ou des bruits anormaux pourraient se produire 1Racc...

Page 23: ...sont entour s d une couche de protection Les tuyaux peuvent tre entour s apr s ou avant avoir t raccord s d une couche de protection allant jusqu 90 3 9 16 D couper la rondelle d fon able du cache tu...

Page 24: ...appareil ext rieur Ligne de transmission raccorder l appareil int rieur Bloc terminal TB3 pour la ligne de transmission Autres Bloc terminal TB7 pour une commande centralis e Une mauvaise connexion e...

Page 25: ...L1 L2 GR RONDELLE POUR GAINE LECTRIQUE accessoire Exemple de syst me de fonctionnement reli la terre avec plusieurs appareils ext rieurs Il est n cessaire d uti liser des c bles blind s et de d finir...

Page 26: ...pouce minimum entre les contacts de chaque p le 2 Utiliser des c bles lectriques en cuivre Utiliser des c bles lectriques correspondant une tension de 300 V Courant total d exploitation de l appareil...

Page 27: ...temp rature ambiante rayons solaires directs eau pluviale etc lors du c blage et du raccordement des appa reils 3 Les dimensions des c bles repr sentent les dimensions minimales pour le c blage de con...

Page 28: ...frig rant ne peut pas s effectuer Attendre 3 minutes apr s l arr t du compresseur avant de r activer les commutateurs SW3 1 et SW3 2 6 Fermer compl tement le robinet d arr t du gaz lorsque le manom t...

Page 29: ...ux et du contr le de la demande se fait par commutation du commutateur DIP 9 2 du panneau de commande ext rieur Les consommations lectriques suivantes par rapport aux valeurs nominales peuvent tre d f...

Page 30: ...el refrigerante indicado R410A para cargar los tubos del refrigerante No lo mezcle con otro tipo de refrigerante y vac e completamente de aire los tubos Si el aire se mezcla con el refrigerante podr a...

Page 31: ...gerante R22 Sustituya las tuercas de abocardado existentes y vuelva a abocardar las seccio nes abocardadas No use tuber as de poco grosor Consulte la p gina 34 Almacene las tuber as que se deban insta...

Page 32: ...ctadas Nombre del modelo de unidad exterior La capacidad de la unidad exterior N mero de unida des que pueden conectarse Intervalo de capaci dades de las unida des conectadas PUMY P36NKMU1 36kBtu h 1...

Page 33: ...aire opcionales para corriente de aire hacia arriba 2 5 3 Cuando instale varias unidades exteriores Deje un espacio de 1 25 mm o m s entre las unidades 1 Obst culos en la parte trasera Fig 2 11 2 Obs...

Page 34: ...Consulte la p gina 31 para las precauciones a tomar en equipos que utilicen el refrigerante R410A y que no se encuentren a continuaci n Utilice aceite de ster de ter o alquilobenceno en peque as cant...

Page 35: ...8 5 16 2 Aseg rese de que los 2 tubos de refrigerante est n aislados para evitar la con densaci n 3 El radio m nimo de curvatura debe ser de 4 100 mm o m s Cuidado Aseg rese de utilizar el aislamient...

Page 36: ...erlos Un radio de curvatura de 100 mm 4 pulg a 150 mm 6 pulg resultar suficiente Aseg rese de que las tuber as no tocan el compresor Podr a producir ruidos o vibraciones extra as 1 Las tuber as se deb...

Page 37: ...ial aislante no se impregnen de agua Las tuber as de refrigerante est n envueltas con una protecci n Los tubos se pueden envolver para su protecci n hasta un di metro de 90 mm 3 9 16 antes de conectar...

Page 38: ...esultante dar lugar a funciones err neas 7 nicamente la l nea de transmisi n especificada deber a ser conectada al bloque de terminal para la transmisi n de la unidad exterior La l nea de transmisi n...

Page 39: ...ornillar en la caja de componentes el ctricos A Fuente de alimentaci n B L nea de transmisi n Ejemplo de un sistema de funcionamiento en tierra con varias unidades exteriores Se requiere cable blindad...

Page 40: ...corriente 3 20 20 20 F0 30 A o menos 2 5 5 10 5 5 10 5 3 10 30 A sensibilidad a la corriente 3 30 30 30 Aplicar a IEC61000 3 3 aproximadamente m x impedancia permitida en el sistema 1 El interruptor d...

Page 41: ...cales 5 Los cables de alimentaci n principal de los componentes de aparatos destinados al uso en la intemperie no deben ser m s livianos que el cable flexible con revestimiento de policioropreno dise...

Page 42: ...3 minutos despu s de que el compresor se haya parado la operaci n de recuperaci n del refrigerante no se puede realizar Espere al menos a que el compresor haya estado parado durante 3 minutos y vuelva...

Page 43: ...comparado con los ndices ajustando SW1 2 Placa del controlador exterior DIP SW9 2 SW1 SW2 Funci n Modo silencioso OFF ON Funcionamiento en modo silencioso Control de demanda ON OFF OFF 100 Normal ON...

Page 44: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment RG79F079H01 Printed in Japan HEAD OFFICE T...

Reviews: