background image

8

4.6.  Additional refrigerant charge

Refrigerant of 3 kg [6.6 lbs] equivalent to 50 m [165 ft] total extended piping length is 
already included when the outdoor unit is shipped. Thus, if the total extended piping 
length is 50 m [165 ft] or less, there is no need to charge with additional refrigerant.

Calculation of Additional Refrigerant Charge

•  If the total extended piping length exceeds 50 m [165 ft], calculate the required 

additional refrigerant charge using the procedure shown below.

•  If the calculated additional refrigerant charge is a negative amount, do not charge 

with any refrigerant.

<Additional Charge>

Additional 
refrigerant charge

=

Liquid pipe size 
Total length of
ø9.52 

×

 0.06 kg 

[3/8" 

×

 0.041 lbs]

+

Liquid pipe size 
Total length of 
ø6.35 

×

 0.024 kg

[1/4" 

×

 0.016 lbs]

Refrigerant  
amount for outdoor 
unit

kg

 [lbs]

(m) 

×

 0.06 (kg/m),

[ft] 

×

 0.041 [lbs/ft]

(m) 

×

 0.024 (kg/m),

[ft] 

×

 0.016 [lbs/ft]

3.0 kg

[6.6 lbs]

<Example>
(Please see the lower half of Fig. 4-1.)
Outdoor model  :  P48
Indoor
1 : P24  A :  ø9.52 [3/8"]  30 m [98 ft] 

a : ø9.52 [3/8"]  15 m [49 ft]

2 : P15       

 

b : ø6.35 [1/4"]  10 m [33 ft]

3 : P08       

 

c : ø6.35 [1/4"]  10 m [33 ft]

4 : P06       

 

d : ø6.35 [1/4"]  20 m [66 ft]

The total length of each liquid line is as follows
ø9.52 [3/8"] : A + a  = 30 m + 15 m = 45 m [98 ft + 49 ft = 147 ft]
ø6.35 [1/4"] : b + c + d = 10 m + 10 m + 20 m = 40 m [33 ft + 33 ft + 66 ft = 132 ft]
Therefore,
<Calculation example>
Additional 
refrigerant charge  = 45 m 

×

 0.06 kg + 40 m 

×

 0.024 kg – 3.0 kg = 0.7 kg (rounded up)

 

= [147 ft 

×

 0.041 lbs + 132 ft 

×

 0.016 lbs – 6.6 lbs = 1.54 lbs]

4.  Installing the refrigerant piping

5.  Drainage piping work

Outdoor unit drainage pipe connection

When drain piping is necessary, use the drain socket or the drain pan (option).

P36·P48

Drain socket

PAC-SG61DS-E

Drain pan

PAC-SG64DP-E

6.1. Caution

1

  Follow ordinance of your governmental organization for technical standard related 

to electrical equipment, wiring regulations and guidance of each electric power 
company.

2

  Wiring for control (hereinafter referred to as transmission line) shall be (5 cm [2 

inch] or more) apart from power source wiring so that it is not influenced by electric 
noise from power source wiring. (Do not insert transmission line and power source 
wire in the same conduit.)

3

  Be sure to provide designated grounding work to outdoor unit.

4

  Give some allowance to wiring for electrical part box of indoor and outdoor units, 

because the box is sometimes removed at the time of service work.

5

  Never connect the main power source to terminal block of transmission line. If 

connected, electrical parts will be burnt out.

6

  Use 2-core shield cable for transmission line. If transmission lines of different 

systems are wired with the same multiplecore cable, the resultant poor transmit-
ting and receiving will cause erroneous operations.

6. Electrical work

7

  Only the transmission line specified should be connected to the terminal block 

for outdoor unit transmission.

 

(Transmission line to be connected with indoor unit : Terminal block TB3 for 
transmission line, Other : Terminal block TB7 for centralized control)

 

Erroneous connection does not allow the system to operate.

8

  In case to connect with the upper class controller or to conduct group operation in 

different refrigerant systems, the control line for transmission is required between 
the outdoor units each other.

 

Connect this control line between the terminal blocks for centralized control. (2-
wire line with no polarity)

 

When conducting group operation in different refrigerant systems without connect-
ing to the upper class controller, replace the insertion of the short circuit connector 
from CN41 of one outdoor unit to CN40.

9

  Group is set by operating the remote controller.

At the 

conditions 

below:

*   The figure to the left is an example 

only. The stop valve shape, service port 
position, etc., may vary according to the 
model.

* Turn 

section 

A

 only.

 

(Do not further tighten sections 

A

 and 

B

 together. )

C

 Charge hose

D

  Service port

Precautions when using the charge valve (Fig.4-8)

Do not tighten the service port too much when installing it, otherwise, the valve core 
could be deformed and become loose, causing a gas leak.
After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten 

it.
Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

Fig. 4-8

Fig. 4-7

B

G

H

E

D

I

(2) 

1

2

(2) Liquid side (Fig. 4-7)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm [5/32 inch] hexagonal wrench. Stop turning when it hits the 
stopper.

 

(ø6.35 [1/4 inch]: Approximately 4.5 revolutions) (ø9.52 [3/8 inch]: Approximately 
10 revolutions)

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

A

 Valve

B

 Unit side

C

 Handle

D

 Cap

E

 Local pipe side

F

 Open position side

G

 Service port

H

 Wrench hole

I

 Refrigerant flow direction

J

 Operation section

Refrigerant pipes are protectively wrapped
•  The pipes can be protectively wrapped up to a diameter of ø90 mm [ø3-35/64 inch] 

before or after connecting the pipes. Cut out the knockout in the pipe cover following 
the groove and wrap the pipes.

Pipe inlet gap
•  Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-

main.

  (If the gaps are not closed, noise may be emitted or water and dust will enter the 

unit and breakdown may result.)

Summary of Contents for PUMY-P NHMU

Page 1: ...MANUAL DE INSTALACI N Para un uso correcto y seguro lea detalladamente este manual y el manual de instalaci n de la unidad interior antes de instalar la unidad de aire acondicionado PARA EL INSTALADO...

Page 2: ...ards The use of any refrigerant other than that speci ed for the system will cause mechanical failure or system malfunction or unit breakdown In the worst case this could lead to a serious impediment...

Page 3: ...ure enters the refriger ant lines refrigeration oil deterioration may result Do not use a charging cylinder If a charging cylinder is used the composition of the refrigerant will change and the ef cie...

Page 4: ...outlet guides for upward air ow 2 4 2 When installing multiple outdoor units Leave 10 mm 13 32 inch space or more between the units 1 Obstacles at rear only Fig 2 8 2 Obstacles at rear and above only...

Page 5: ...d cause damage or injuries The unit must be installed according to the instructions in order to minimize the risk of damage from earthquakes typhoons or strong winds An incor rectly installed unit may...

Page 6: ...ze adjustment gauge can be used to con rm A measurements Warning When installing the unit securely connect the refrigerant pipes before start ing the compressor A Liquid pipe Gas pipe PUMY 9 52 3 8 15...

Page 7: ...lant to seal the ends of the thermal insulation around the pipe connection sections to prevent water from entering the thermal insulation Note Triple Evacuation Evacuate the system to 4 000 microns fr...

Page 8: ...nsmission lines of different systems are wired with the same multiplecore cable the resultant poor transmit ting and receiving will cause erroneous operations 6 Electrical work 7 Only the transmission...

Page 9: ...e same group to the terminal block on the remote controller RC d Connect together terminals M1 M2 and terminal S on the terminal block for central control TB7 for the outdoor unit OC e The jumper conn...

Page 10: ...hat generated overcurrent may include some amount of direct current Caution Some installation site may require attachment of an earth leakage breaker If no earth leakage breaker is installed it may ca...

Page 11: ...er carry out pump down operation if the amount of refrigerant inside the indoor unit is larger than the amount of charge less refrigerant Carrying out a pump down operation when the amount of refriger...

Page 12: ...rminales Asimismo no empalme nunca los cables al realizar el cableado a menos que se indique lo contrario en este documento El hecho de no seguir estas instrucciones puede provocar un sobrecalenta mie...

Page 13: ...gua de postes de iluminaci n o de tel fono Si la unidad no est bien conectada a la l nea de tierra se puede producir una descarga el ctrica Utilice disyuntores interruptor de falta de tierra interrupt...

Page 14: ...unidades correlativas Adem s se debe dejar el espacio indicado No utilice las gu as para salida de aire opcionales para corriente de aire hacia arriba 3 Obst culos s lo en la parte delantera Fig 2 10...

Page 15: ...otros peligros Usar un refrigerante distinto al indicado para el sistema provocar un fallo mec nico un funcionamiento defectuoso del sistema o la aver a de la unidad En el peor de los casos podr a sup...

Page 16: ...gerante R410A Para con rmar las medidas de A se puede utilizar el ajustador del tama o Atenci n Al instalar la unidad conecte rmemente las tuber as de refrigerante antes de poner en marcha el compreso...

Page 17: ...s ya que funcionan como selladoras para evitar fugas de refrigerante 5 Utilice un sellador para proteger las conexiones de los tubos y los extremos del material aislante no se impregnen de agua Nota V...

Page 18: ...las l neas de transmisi n de sistemas diferentes est n conectados con los mismos cables de varias almas la pobre transmisi n y recepci n resultante dar lugar a funciones err neas 6 Trabajo el ctrico 7...

Page 19: ...itud de esta secci n L8 deber a incluirse en longitud m xima de c lculo y la longitud total 2 Controlador remoto MA Longitud mayor a trav s de las unidades exteriores Cable M NET L1 L2 L3 L4 y L1 L2 L...

Page 20: ...iesgo de que se produzca calentamiento o un incendio Aseg rese de escoger un interruptor de protecci n de sobrecarga adecuado No olvide que la sobrecorriente generada puede contener peque as cantidade...

Page 21: ...r y vuelva a colocar el tap n a cada v lvula de parada Notas 1 Nunca realice el vaciado si la cantidad de refrigerante del interior de la unidad interior es superior a la cantidad de refrigerante no c...

Page 22: ...nt sans tension sur les bornes Ne jamais effectuer de jonction sur les c bles sauf en cas d indications contraires Le non respect de cette consigne peut entra ner une surchauffe ou un incendie Le couv...

Page 23: ...te de l appareil peut provoquer un choc lectrique Utiliser des coupe circuits disjoncteur de fuite la terre interrupteur d isolement fusible B et disjoncteur bo tier moul la capacit sp ci e Si la capa...

Page 24: ...pacer galement les appareils comme illustr Ne pas utiliser les guidages de sortie d air en option pour un d bit d air vers le haut 3 Obstacles uniquement l avant Fig 2 10 Lors de l utilisation d un gu...

Page 25: ...frig rant diff rent de celui sp ci pour le climatiseur peut en tra ner des d faillances m caniques des dysfonctionnements du syst me ou une panne de l appareil Dans le pire des cas cela peut entra ne...

Page 26: ...au tableau 1 pour l vasement des tuyaux de r frig rant R410A La jauge de r glage de la taille peut tre utilis e pour con rmer les mesures A Avertissement Pendant l installation de l appareil brancher...

Page 27: ...de l isolation thermique autour des sections de raccordement des tuyaux a n d emp cher l eau de p n trer dans l isolation thermique Remarque Triple vacuation vacuez le syst me de 4 000 microns par le...

Page 28: ...ts syst mes devaient tre reli es par le m me c ble ls multiples la transmission et la r ception seraient mauvaises ce qui conduirait un fonctionnement erron des appareils 6 Installations lectriques 7...

Page 29: ...IC qui poss de l adresse la plus r cente au sein d un m me groupe au bloc terminal de la commande distance RC d Connecter les bornes M1 M2 et S des blocs terminaux TB7 pour le contr le central sur les...

Page 30: ...ous d utiliser le correct interrupteur de protection contre la surintensit de courant Veuillez noter que la surintensit de courant g n r e peut comprendre une certaine quantit de courant direct Pr cau...

Page 31: ...rr t Remarque 1 Ne jamais proc der au pompage si la quantit de r frig rant dans l appareil int rieur est sup rieure la quantit de r frig rant sans charge suppl mentaire Le pompage lorsque la quantit d...

Page 32: ...on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CH...

Reviews: