Start … Press the mode switch and dehumidifying switch when power is off.
Turn on the power with those switches pressed.
●
Operational content
①
Dehumidifying operation (High)
②
Heater turns on immediately.
③
Humidity sensor check mode starts.
④
Louvre speed 243pps (high speed mode)
⑤
Detection of room temperature anomaly is released.
⑥
Determining the detection of temperature anomaly of heat exchanger and heater once for all
⑦
When an error occurs, the indications shown in “ 3) Error Indications and Corrective Actions”
are displayed.
4) Self Diagnostic Test Program
5) Demo Program
6) Error History Display
●
Start … Press the mode switch and the dehumidifying switch 7 times together when power is off.
Turn on the power within 2 seconds.
Alternatively, turn on the power with the swing louvre switch pressed.
●
Operational content … operation without heater continuity
●
Release … Remove the power plug.
●
Start … Press the mode switch and the dehumidifying switch 9 times together when power is off.
Turn on the power within 2 seconds.
●
Mode selection … Change to the diagnosis mode with the mode switch.
History1(newest)
→
History2
→
History3
→
History4
→
History5
→
History6
→
History7
→
History8
→
(History1)
●
Release … Turn off the power.
●
Release… Turn off the power.
26