Error (failure)
P10 connector out of position
Room temperature thermistor blowout
Check the P10 connection.
Check the room temperature and humidity sensor
board.
Corrective action
Room temperature thermistor short
Room temperature and humidity
sensor board failure
P11 connector out of position
Tube temperature thermistor blowout
Check the P11 connection.
Check the tube temperature thermistor.
Tube temperature thermistor short
Tube temperature sensor failure
Microprocessor failure
RAM error
Replace the main board.
Frequency determination error
(When power is on)
Outlet/power check
(Replace the main and power supply boards.)
Watchdog timer error
Replace the main board.
Compressor
Check blowing performance.
Check the tube temperature thermistor.
Check the compressor operating noise.
Indication
(Timer display)
E0
E1
E7
E8
A1
A2
A3
A6
P4
Frequency determination error
(During operation)
8.3 Error Indications and Corrective Actions
8.4 Self-Test Program and Execution Procedure
(1) Deactivating 3-minute restart prevent lock
●
Start:
Press the MODE and HUMIDITY SELECTION buttons together 3 times when the power
is off. Press the POWER button within 2 seconds.
●
Functions:
1
Deactivates 3-minute restart prevention lock (immediate operation)
2
Fan: Fix at rank 6 (max. airflow)
3
Activates compressor
4
Operating mode: Low Temp
5
Low temperature is indicated on LCD.
6
When EEPROM error is detected, water full,
mildew guard elite
, air purifying and LED are lit.
●
To end:
Turn power off. The solenoid valve functions for 3 seconds.