Easy Dehumidifier
1. Controls
(a) Adjusts humidity according to room temperature for increased comfort.
(b) CIRCULATION mode is activated when the temperature is high and the humidity is low. This mode keeps the
compressor off.
(c) Switches temperature table every 60 seconds to prevent the blower from turning on and off at the 3-minute restart for
the coloured section in the chart above. (51% – 59%)
(d) When the room temperature is above 29
°
C (temperature rising) or 27
°
C (temperature decreasing), CIRCULATE
mode operates with the humidity below 50%.
(e) The unit activates the dehumidifier when the humidity rises above 60%, and returns to CIRCULATE mode when the
humidity drops below 50%.
0
60%
ON
ON
OFF
OFF
OFF
OFF
ON
ON
60%
60%
50%
50%
50%
1
2
3
Current humidity
– Set humidity
20
°
C
27
°
C
34
°
C
+3%
–1%
+5%
+1%
Temperature
Temperature table
Set humidity
Dehumidification
Fan rank
Compressor
Fan rank
Compressor
Fan rank
Compressor
22
°
C
29
°
C
36
°
C
Rank 3
Rank 1
ON
ON
Rank 3
Rank 1
Rank 3
Rank 2
ON
ON
Circulate
To
Dehumidifier
mode
To
Dehumidifier
mode
Rank
3
Rank 0
Rank 0
Rank 5
To
Circulate
mode
Rank 5
Rank 5
To
Circulate
mode
Dehumidifier mode
Circulate
Dehumidifier mode
Dehumidifier mode
Dehumidifier mode
Circulate
set humidity 60%
Dehumidifier mode
set humidity 50%
Circulate
set humidity 60%
Set humidity 60%
Set humidity 50%
ON
OFF
ON
OFF
50%
60%
Humidity
Compressor
Blower
~20
°
C~
~27
°
C~
Temperature
Target part
Compressor
Airflow fan
Solenoid valve
Louvre
Operation
ON/OFF
Rank control
OFF
ON/OFF
2. Easy DEHUMIDIFYING mode is disabled in the following cases.
(a) The MODE button is used to activate the previously set mode (HIGH, LOW, AUTO, MILDEW GUARD, LOW TEMP).
(b) The selection button is used to activate LAUNDRY mode.
(c) The air purifier button is used to activate AIR PURIFIER mode.
Room
temperature
Humidity
Set humidity
60%
Set humidity
50%
When 60% exceeded,
lowers to below 50%
Compressor
OFF
Fan rank 0
Compressor
OFF
Fan rank 0
CIRCULATE mode
60%
50%
20°C
27°C