4 SYSTEM CONFIGURATION
4.5 Rules of System Configuration and Examples of Reconfiguration
59
4
Check of limitation on the number of modules
Check if the example system configuration is within the connectable-module range.
■
Number of connected expansion adapters
(
Page 44 Number of connected expansion adapters)
■
Number of connected extension modules
• Number of modules connected on whole system
(
Page 44 Overall system limitation)
• Number of modules connected to the CPU module
(
Page 45 Connection to the CPU module)
• Number of modules connected to extension power supply module
(
Page 46 Connection to the extension power supply module)
• Number of modules connected to the bus conversion module
(
Page 46 Connection to the bus conversion module (connection with FX3 extension devices))
Type
No. of modules used
Limitations
Judgment
Expansion adapter (Communication)
2
Up to 2
OK
Type
No. of modules used
Limitations
Judgment
Extension module
11
(Extension power supply
modules, connector
conversion module are
excluded.)
Up to 16
(Extension power supply modules, connector
conversion module are excluded.)
OK
Extension power supply module
1
Up to 2
OK
Connector conversion module
1
Only 1
OK
Bus conversion module
1
Only 1
OK
Type
No. of modules used
Limitations
Judgment
Total No. of I/O modules, intelligent function modules, and bus conversion modules
3
Up to 12
OK
Total No. of intelligent function module and bus conversion modules
0
Up to 8
OK
Type
No. of modules used
Limitations
Judgment
Total No. of I/O modules, intelligent function modules, and bus conversion modules
8
Up to 10
OK
Total No. of intelligent function module and bus conversion modules
7
Up to 8
OK
Type
No. of modules used
Limitations
Judgment
Total No. of intelligent function modules
5
Up to 6
OK