APPX
Appendix 4 I/O Module
149
A
■
Relay output
Item
Specifications
No. of output points
FX5-8EYR/ES
8 points
FX5-16EYR/ES
16 points
FX5-16ER/ES
8 points
FX5-32ER/DS
16 points
Connection type
Terminal block (M3 screws)
Output type
Relay
External power supply
30 V DC or less
240 V AC or less
(250 V AC or less when the module does not comply with CE, UL, or cUL standards)
Output circuit insulation
Mechanical insulation
Indication of output operation
LED is lit when output is on
Max. load
2 A/point
The total load current of resistance loads per common terminal should be the following value.
• 4 output points/common terminal: 8 A or less
• 8 output points/common terminal: 8 A or less
Open circuit leakage current
Min. load
5 V DC, 2 mA (reference values)
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Output circuit configuration
Load
DC power supply
Fuse
Fuse
AC power supply
Y
COM0
Y
COM1