19
6.2 Use of E/P regulator
When using an air clutch/brake instead of the powder
clutch/brake or the hysteresis clutch/brake, the control out-
put of 4 to 20 mA (load resistance to be 470
Ω
or less) can
be supplied to the electric-pneumatic regulator.
The control output of 0 to 100% at this stage corresponds
to 4 to 20 mA.
Adjust the zero/span of the electric-pneumatic regulator so
that the specified output may be generated in response to
the control output of 0 to 100%.
• When using an electric-pneumatic regulator of 4 to
20 mA input current type, connect it as per the fig-
ure shown on the right.
• When using an electric-pneumatic regulator of 0 to
5V voltage input type, connect it between termi-
nals SA and SN.
• Use the "ACTUATOR" screen within "SWITCH" on the initial setting screen or the engineer screen to
set or change the settings.
• Use this output in powder mode. It can not be used in AC servo mode.
0
20
40
60
80
100
0
4
20
→
Out
put cu
rrent
(mA
)
→
Control output (%)
1. Wiring
4~20mA
E/P
Regulator
EAP
EAN
470
Ω
or less
2. Setting
A
T U A T O R
S E L E C T
A C T U A T O R
P O W D E R
:
A C
S E R V O
M O T O R
C
Select "POWDER"