5 - 17 5 - 17
MELSEC-Q
5 UTILITY PACKAGE (GX Configurator-DA)
[Explanation of items]
(1) Contents of screen display
Setting item
: Buffer memory name is displayed.
Current value
: Current value of the buffer memory is monitored.
Setting value
: Select or enter the data to be written into the buffer memory
during test operation.
(2) Explanation of the command buttons
Current value
The current value of the selected item is displayed. (This is
used to check text that cannot be displayed in the current
value field. However, in this utility package, all items can be
displayed in the display fields).
Make text file
Creates a file consisting of the screen contents in text file format.
Start monitor /
Stop monitor
Selects whether or not the current value fields are monitored.
Execute test
Performs a test of the selected item. To select more than one
item, select multiple items while holding down the Ctrl key.
Close
Closes the screen currently displayed and returns to the
previously displayed screen.
POINT
(1) Turning the output enable/disable flag ON/OFF or writing the CH digital value
during test operation changes the analog output, so perform these after taking
ample safety precautions.
REMARK
The selection test operation is explained below using the CH1 digital value writing as
an example.
(1) Change the setting value field for "Y01: CH.1 output enable/disable flag" to "ON:
enable."
At this point, the value is not yet written in the D/A conversion module.
(2) Click and select the setting value field to be written in the D/A conversion
module.
To write several data items at one time, perform the selection operation while
holding down the Ctrl key.
(3) Click the Execute test to execute write operation.
Once writing has been completed, the value that was written will be displayed in
the present value field.