4 - 10 4 - 10
MELSEC-Q
4 SETUP AND PROCEDURES BEFORE OPERATION
(2) Operating procedure
Start the settings with GX Developer I/O assignment setting screen.
(a) I/O assignment setting screen
Set the following for the slot in which the D/A
conversion module is mounted.
The type setting is required; set other items as
needed.
Type
Model name
Points
Start XY
Detailed
setting
: Select "intelli."
: Enter the module model name.
: Select 16 points.
: Enter the start I/O number for the
D/A conversion module.
: Specify the control PLC for the
D/A conversion module.
It is unnecessary to set the "Error
time output mode" or "H/W error
time PLC operation mode" since
these settings are invalid for the
D/A conversion module.
(b) Switch setting for intelligent function module screen
Click on [Switch setting] on the I/O assignment
setting screen to display the screen shown at the
left, then set switches 1 to 5.
The switches can easily be set if values are
entered in hexadecimal. Change the entry format to
hexadecimal and then enter the values.