Appendix 1 Parameter List (FR-E700)
Parameters significantly vary depending on model of device. The parameter list for the FR-E700 model is included
in this document.
Make sure to read the specific manual for your device if your environment contains different devices.
Parameter
Name
Setting range Initial value
0
Torque boost
0 to 30%
6/4/3/2%
*1
1
Upper-limit frequency 0 to 120Hz
120Hz
2
Lower-limit frequency 0 to 120Hz
0Hz
3
Base frequency
0 to 400Hz
60Hz
4
Multi-speed setting
(high speed)
0 to 400Hz
60Hz
5
Multi-speed setting
(middle speed)
0 to 400Hz
30Hz
6
Multi-speed setting
(low speed)
0 to 400Hz
10Hz
7
Acceleration time
0 to 3600/360s 5/10/15s
*2
8
Deceleration time
0 to 3600/360s 5/10/15s
*2
9
Electronic thermal
O/L relay
0 to 500A
Inverter
rated
current
10
DC injection brake
operation frequency 0 to 120Hz
3Hz
11
DC injection brake
operation time
0 to 10s
0.5s
12
DC injection brake
operation voltage
0 to 30%
6/4/2%
*3
13
Starting frequency
0 to 60Hz
0.5Hz
14
Load pattern
selection
0 to 3
0
15
Jog frequency
0 to 400Hz
5Hz
16
Jog acceleration/
deceleration time
0 to 3600/360s 0.5s
17
MRS input selection 0, 2, 4
0
18
High speed
upper-limit frequency 120 to 400Hz 120Hz
19
Base frequency
voltage
0 to 1000V,
8888, 9999
9999
20
Acceleration/
deceleration
reference frequency
1 to 400Hz
60Hz
21
Acceleration/
deceleration time
increments
0, 1
0
22
Stall prevention
operation level
0 to 200%
150%
23
Stall prevention
operation level
compensation factor
at double speed
0 to 200%,
9999
9999
24
Multi-speed setting
(speed 4)
0 to 400Hz,
9999
9999
Parameter
Name
Setting range Initial value
25
Multi-speed setting
(speed 5)
0 to 400Hz,
9999
9999
26
Multi-speed setting
(speed 6)
0 to 400Hz,
9999
9999
27
Multi-speed setting
(speed 7)
0 to 400Hz,
9999
9999
29
Acceleration/
deceleration pattern
selection
0, 1, 2
0
30
Regenerative
function selection
0, 1, 2
0
31
Frequency jump 1A 0 to 400Hz,
9999
9999
32
Frequency jump 1B 0 to 400Hz,
9999
9999
33
Frequency jump 2A 0 to 400Hz,
9999
9999
34
Frequency jump 2B 0 to 400Hz,
9999
9999
35
Frequency jump 3A 0 to 400Hz,
9999
9999
36
Frequency jump 3B 0 to 400Hz,
9999
9999
37
Speed display
0 to 0,01 to
9998
0
40
RUN key rotation
direction selection
0, 1
0
41
Up-to-frequency
sensitivity
0 to 100%
10%
42
Output frequency
detection
0 to 400Hz
6Hz
43
Output frequency
detection for reverse
rotation
0 to 400Hz,
9999
9999
44
Second
acceleration/
deceleration time
0 to 3600/360s 5/10/15s
*2
45
Second deceleration
time
0 to
3600/360s,
9999
9999
46
Second torque
boost
0 to 30%,
9999
9999
47
Second V/F
(base frequency)
0 to 400Hz,
9999
9999
48
Second stall
prevention operation
current
0 to 200%,
9999
9999
Summary of Contents for FREQROL-E700