5-13
5
5.2.5 Inverter communication settings
Configure communication parameters on the inverter parameter unit (PU) in advance before connecting the
inverter to the programmable controller. Be sure to perform the inverter reset after updating each parameter.
Communication setting details (required parameters)
The following table lists the parameters that must be configured.
Pr.
Parameter
Setting
Contents of setting
Pr.117
PU communication station number
0 to 31 Up to 16 inverters can be connected
Pr.118
PU communication speed
48
4800bps
96
9600bps
192
19200bps
384
38400bps
Pr.119
PU communication stop bit length
10
Data length: 7 bits
Stop bit: 1 bit
Pr.120
PU communication parity check
2
Even parity
Pr.123
PU communication waiting time setting 9999
Configured with communication data
Pr.124
PU communication CR/LF selection
1
With CR, without LF
Pr.79
Operation mode selection
0
External operation mode when power is first turned
on
Pr.549
Protocol selection
0
Mitsubishi inverter protocol (computer link)
Pr.340
Communication startup mode selection 1 or 10 1: Network operation mode
10: Network operation mode (the PU operation mode
and network operation mode can be changed
from the operation panel)