2-9
2
● Blade terminals
Strip the sheath off of wires, and connect them to a blade terminal.
Sleeve
Shell
Wi
re
0 to 0.5m
m
Damaged
Crumpled tip
Unstranded wires
Wires are not inserted
into the shell
10mm
Cable sheath stripping length
1.
Strip off the sheath about the size below. If the length of the sheath peeled is too long, a short circuit may
occur among neighboring wires. If the length is too short, wires might come off.
Wire the stripped wire after twisting it to prevent it from becoming loose. In addition, do not solder it.
2.
Crimp the blade terminal.
Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5mm from a sleeve.
Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimp-
ing is inappropriate, or the face is damaged.
● When using stranded wires without a blade terminal, twist enough to avoid short circuit with a nearby
terminals or wires.
● Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an
inverter damage or injury.
CAUTION