228
FDTN-H
Outdoor air W.B. temperature (˚CW.B.)
Indoor air W.B. temperature (˚CW.B.)
ISO-T1 Standard condition
(b)
Only case of ISO-T1 models (Including 308HEN-S, 308HES-S, 408HES-S, 508HES-S type)
Indoor air W.B. temperature (˚CW.B.)
ISO-T1 Standard condition
Outdoor air D.B.
temperature (˚CD.B.)
Cooling operation
Indoor air D.B.
temperature (˚CD.B.)
Heating operation
Coefficient of cooling and heating capacity
in relation to temperatures
Outdoor air D.B.
temperature (˚CD.B.)
Cooling operation
Indoor air D.B.
temperature (˚CD.B.)
Heating operation
Coefficient of cooling and heating
capacity in relation to temperatures
6.2.6
Selection chart
Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be obtained in
the following way.
Net capacity = Capacity shown on specification
×
Correction factors as follows.
(1)
Coefficient of cooling and heating capacity in relation to temperatures
(a)
Only case of ISO-T1 models (Except 308HEN-S, 308HES-S, 408HES-S, 508HES-S type)
ISO-T1 Standard condition
Outdoor air W.B. temperature (˚CW.B.)