(a)
Accessories
Confirm accessories shown below are attached in the bag with this installation manual.
1)
“Edging” for protection of electric wires from opening edge.
(b) Selection of installation location
Select the installation location after obtaining the approval of customer.
1)
The place where the foundation can bear the weight of Outdoor unit.
2)
The place where there is no concern about leakage of combustible gas.
3)
The place where it is not stuffy.
4)
The place where free from thermal radiation of other thermal source.
5)
The place where flow of drain is allowed.
6)
The place where noise and hot air blast do not trouble neighboring houses.
7)
The place where there is no obstruction of wind at the intake air port and discharge air port.
5) Couple the upper case with the lower case as it was to
finish up the installation.
Cautions for extension of remote controller cords
●
Make sure to use shielding wires only.
•
All models: 0.3 mm
2
x 3 core wires [MVVS3C,
products of Keihan Cables]
Note (1) When the extension distance exceeds 100 m, change the
wire size as follows:
100 ~ 200 m ... 0.50 mm
2
⳯
3 core wires
~ 300 m ... 0.75 mm
2
⳯
3 core wires
~ 400 m ... 1.25 mm
2
⳯
3 core wires
~ 600 m ... 2.00 mm
2
⳯
3 core wires
●
Make sure to ground one side only of the
shielding wire.
6.5.3
Installation of outdoor unit
O
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGIN-
NING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD
CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/
OR PROPERTY DAMAGE.
1) Set necessary functions in accordance with the model of indoor
unit.
Refer to (c) for the setting of functions.
2) Couple the upper case with the lower case as they were.
3) Secure the remote controller cords on the wall or other using cord
clamps.
Embedded installation
1) Have a JIS box and remote controller cords (use shielding wires
or twisted pair wires for extension) embedded in the wall in
advance.
Adequate JIS box
●
JIS C 8336
Single switch box (without cover)
●
JIS C 8336
Medium size square outlet box and two-switch cover
with paint margin
2) Remove the upper case from the remote controller.
3) Secure the remote controller body on the JIS box with 2 pieces of
M4 round head screw (provided by customer).
4) Connect remote controller cords with the remote controller.
(Refer to the section regarding the exposed installation.)
M4 round head screw x 2 pieces
(Provided by customer)
JIS box
(Provided by customer)
Remote controller cords