227
FDTN-H
Preset point of the protective devices
Parts name
Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for detecting dis-
charge pipe temp.)
Thermistor
(for detecting heat
exchange temp.)
High pressure switch
(for controlling FM
0
)
OFF 68˚C
ON 61˚C
Equipped
unit
Th
I-
R
Tho-D
Tho-R
63H
2
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
FDTN308~508
(FDC308~508 type only)
FDT308~508
OFF 2.5˚C
ON 10˚C
OFF 135˚C
ON 90˚C
OFF 70˚C
ON 60˚C
OFF 2.5MPa (25.5 Kgf/cm
2
G)
ON 2.06MPa (21 kgf/cm
2
G)
Parts name
Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Defrost thermostat
High pressure switch
(for controlling FMo)
OFF 68˚C
ON
61˚C
Equipped
unit
TH
I-
R
23DH
2
23DH
1
63H
2
Indoor unit
Outdoor unit
Outdoor unit
FDTN208~508
(FDC208, 258 or FDC206~506 type only)
FDT208~508
OFF 2.5˚C
ON
10˚C
OFF 12˚C
ON
-6˚C
OFF 2.5MPa (25.5 Kgf/cm
2
G)
ON 1.86MPa (19 kgf/cm
2
G)
Summary of Contents for FDT208HEN-S