265
FDTN-H
Item
Model
FDC208H type
FDC258H type
FDC308H type
FDC408H type
FDC508H type
FDC208C type
FDC258CEN3
FDC258CEP3
Factory charge amount
(kg)
Additional charge amount
1 (kg/m)
Pipe length that
additional charge is not
required (m)
Maximum piping
length (m)
0.98
1.10
1.40
1.67
1.90
0.90
1.05
1.13
0.015
0.025
0.035 2
0.015
0.025
–
–
0.02
–
0 ~30m
30 ~ 50m
0 (5) *3
5
0 (5) *3
5
30
50
30
¡
In the case of recharge the refrigerant for service, calculate the proper amount of refrigerant depending on the piping length on
site.
Example : In the case that FDTN508HES-S with piping length of 15m is fully recharged in service.
1.9 (kg) + (15 – 5) (m)
×
0.035 (kg/m)= 2.25 (kg)
Recharge amount.
Additional charge amount per 1m.
Length that additional charge is not required.
Total length of the piping (one way).
Factory charge amount for FDC508HES3.
Note (1) *3. The values in ( ) are when connected to FDKN Series indoor unit.
1 Additional charge amount
(4)
Drain piping work
¡
Execute the drain piping by using field purchased parts of pipe, elbow, and grommets, if the drainage work is needed.
Drain elbow (1 pc.)
™
There are 3 holes (ø 20) on the bottom plate of Outdoor
unit for draining condensed water.
™
To guide the condensed water to the gutter it is necessary
to install the unit on the flat base or blocks.
™
Connect the drain elbow as shown in the illustration and
close other holes with grommets.
Drain grommet
(2 pcs.)
Hard vinyl chloride pipe for
general purpose (VP-16)
¡
Calculate the additional charge amount according to Table 1.
Example : In the case that FDTN508HES-S is newly installed with piping length of 40m.
(30 – 5) (m)
×
0.035 (kg/m) + (40 – 30) (m)
×
0.02 (kg/m)= 1.075 (kg)
Additional charge amount.
When piping length is more than 30m,
additional charge amount per 1m.
Total length of the piping (one way).
When piping length is 30m or less, additional charge amount per 1m.
Length that additional charge is not required.
30 m
50 m
0.02kg/m
Outdoor Unit
Indoor Unit
0 m
2
(d) Refrigerant charge
1)
Outdoor unit is pre-charged R-22 refrigerant at a factory as shown in Table 1.
2)
Indoor unit is pre-charged only a small amount of nitrogen gas for prevention of the air entry.
3)
Additional charge on site is required when the pipe length is longer than that of restricted value (Which is varied wirh the
type of Indoor unit) as shown in Table 1.
Table 1