 Before installing the unit, make sure you read all the “Safety 

precautions”.

 Please report to your supply authority or obtain their consent before 

connecting this equipment to the power supply system.

 Warning:

Describes precautions that must be observed to prevent danger of injury or

death to the user.

 Caution:

Describes precautions that must be observed to prevent damage to the unit.

After installation work has been completed, explain the “Safety Precautions,” use, 

and maintenance of the unit to the customer according to the information in the 

Operation Manual and perform the test run to ensure normal operation. Both the 

Installation Manual and Operation Manual must be given to the user for keeping. 

These manuals must be passed on to subsequent users.

Contents

 Warning:

•  Ask the dealer or an authorized technician to install the air conditioner.

•  Install the unit at a place that can withstand its weight.

•  Use only specified cables for wiring. The wiring connections must be 

made securely with no tension applied on the terminal connections. Also, 

never splice the cables for wiring (unless otherwise indicated in this 

document).

  Failure to observe these instructions may result in overheating or a fire.

•  Use only accessories authorized by Mitsubishi Electric and ask the dealer 

or an authorized technician to install them.

•  Do not touch the heat exchanger fins.

•  Install the air conditioner according to this Installation Manual.

•  Have all electric work done by a licensed electrician according to local 

regulations.

•  If the air conditioner is installed in a small room, measures must be taken 

to prevent the refrigerant concentration from exceeding the safety limit 

even if the refrigerant should leak.

•  The cut face punched parts may cause injury by cut, etc. The installers are 

requested to wear protective equipement such as gloves, etc.

•  When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it 

with any other refrigerant and do not allow air to remain in the lines.

   If air is mixed with the refrigerant, then it can be the cause of abnormal 

high pressure in the refrigerant line, and may result in an explosion and 

other hazards.

   The use of any refrigerant other than that specified for the system will 

cause mechanical failure or system malfunction or unit breakdown. In the 

worst case, this could lead to a serious impediment to securing product 

safety.

1.  Safety precautions

  : Indicates an action that must be avoided.

  : Indicates that important instructions must be followed.
  : Indicates a part which must be grounded.

 : Indicates that caution should be taken with rotating parts.

  : Indicates that the main power switch must be turned off before servicing.

 : Beware of electric shock.
 : Beware of hot surface.

ELV

 : At servicing, please shut down the power supply for both the Indoor and 

Outdoor Unit.

 Warning:

Carefully read the labels affixed to the main unit.

 Caution:

•  Do not use the existing refrigerant piping, when use R410A or R407C 

refrigerant.

•  Use ester oil, either oil or alkylbenzene (small amount) as the refrigerator 

oil to coat flares and flange connections, when use R410A or R407C 

refrigerant.

•  Do not use the air conditioner where food, pets, plants, precision 

instruments, or artwork are kept.

•  Do not use the air conditioner in special environments.

•  Ground the unit.

•  Install an leak molded case circuit braker, as required.

•  Use power line cables of sufficient current carrying capacity and rating.

•  Use only a molded case circuit braker and fuse of the specified capacity.

•  Do not touch the switches with wet fingers.

•  Do not touch the refrigerant pipes during and immediately after operation.

•  Do not operate the air conditioner with the panels and guards removed.

•  Do not turn off the power immediately after stopping operation.

Fig. -1

.  Installation location

.1.  Outline dimensions (Indoor unit) (Fig. -1)

Select a proper position allowing the following clearances for installation and 

maintenance.

 PKFY-P·VHM-E

(mm)

A

B

C

D

E

Min. 150

Min. 50

Min. 50

Min. 250

Min. 220

Air outlet: Do not place an obstacle within 1500 mm of the air outlet.

Floor surface

Furnishing

When the projection dimension of a curtain rail or the like from the wall exceeds 60 mm, 
extra distance should be taken because the fan air current may create a short cycle.

1800 mm or greater from the floor surface (for high location mounting)

55 mm or greater with left or rear left piping and optional drain pump installation

550 mm or greater with optional drain pump installation

Minimum 7 mm: 250 mm or greater with optional drain pump installation

 PKFY-P·VHM-E

G

F

A

B

L

898

295

H

E

J

*

M

I

D

C

249

K

(mm)

1.  Safety precautions .............................................................................................2

2.  Installation location ............................................................................................2

3.  Installing the indoor unit ....................................................................................3

4.  Installing the refrigerant piping ..........................................................................6

5.  Drainage piping work .........................................................................................8

6.  Electrical work ...................................................................................................9

7.  Test run (Fig. 7-1) ............................................................................................10

Note:

The phrase “Wired remote controller” in this installation manual refers only to the PAR-1MAA.

If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are 

included in these boxes.

RG79D840H01_en.indd   2

2012/10/25 (木)   午後 4:10:27

Summary of Contents for City Multi PKFY-P

Page 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Page 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Page 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Page 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Page 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Page 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Page 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Page 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Page 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Page 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Page 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Reviews: