5

GB

.  Installing the indoor unit

Left and left rear piping (Fig. -8)

4. Drain hose replacement 

 See 5. Drainage piping work.

  Be sure to replace the drain hose and the drain cap for the left and rear left 

piping. Dripping may occur if you forget to install or fail to replace these parts.

C

  Drain cap 

1) Be careful that the drain hose is not raised, and that contact is not made with 

the indoor unit box body. 

2) Securely wrap the felt tape 

3

 starting from the base. (Overlap the felt tape at 

one-half of the tape width.) 

3)  Fasten the end portion of the felt tape 

3

 with vinyl tape. 

Cut off for left piping.

Fig. -8

C

D

1)

3)

2)

Fig. -9

Fig. -10

Fig. -11

B

A

C

D

A

C

B

C

A

B

 PKFY-P·VHM-E

.5.  Mounting the indoor unit

1. Affix the mount board 

1

 to the wall.

2. Hang the indoor unit on the hook positioned on the upper part of the mount 

board.

Rear, right and lower piping (Fig. -9)

3. While inserting the refrigerant piping and drain hose into the wall penetration 

hole (penetration sleeve), hang the top of the indoor unit to the mount board 

1

.

4. Move the indoor unit to the left and right, and verify that the indoor unit is hung 

securely.

5. Fasten by pushing the bottom part of the indoor unit onto the mount board 

1

(Fig. 3-10)

*  Check that the knobs on the bottom of the indoor unit are securely hooked into 

the mount board 

1

.

6. After installation, be sure to check that the indoor unit is installed level.

Mount board 

1

Indoor unit

Hook

Square hole

Left and left rear piping (Fig. -11)

3. While inserting the drain hose into the wall penetration hole (penetration sleeve), 

hang the top of the indoor unit to the mount board 

1

.

  Giving consideration to the piping storage, move the unit all the way to the left 

side, then cut part of the packaging carton and wrap into a cylindrical form as 

illustrated in the diagram. Hook this to the rear surface rib as a spacer, and raise 

the indoor unit. 

4. Connect the refrigerant piping with the site-side refrigerant piping. 

5. Fasten by pushing the bottom part of the indoor unit onto the mount board 

1

*  Check that the knobs on the bottom of the indoor unit are securely hooked into 

the mount board 

1

6. After installation, be sure to check that the indoor unit is installed level.

A

  Indoor unit 

B

  Packaging cushion

C

  Block of cushion 

5

RG79D840H01_en.indd   5

2012/10/25 (木)   午後 4:10:31

Summary of Contents for City Multi PKFY-P

Page 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Page 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Page 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Page 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Page 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Page 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Page 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Page 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Page 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Page 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Page 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Reviews: