Flare cutting dimensions

Copper pipe O.D.  

(mm)

Flare dimensions  

øA dimensions (mm)

ø6.35

8.7 - 9.1

ø9.52

12.8 - 13.2

ø12.7

16.2 - 16.6

ø15.88

19.3 - 19.7

ø19.05

22.9 - 23.3

Refrigerant pipe sizes & Flare nut tightening torque

C

  Do not apply refrigerating machine oil to the screw portions.  

(This will make the flare nuts more apt to loosen.)

Be certain to use the flare nuts that are attached to the main unit.  

(Use of commercially-available products may result in cracking.)

R407C or R22

R410A

Flare nut O.D.

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

Pipe size O.D.  

(mm)

Tightening 

torque.  

(N·m)

Pipe size O.D.  

(mm)

Tightening 

torque.  

(N·m)

Pipe size O.D.  

(mm)

Tightening 

torque.  

(N·m)

Pipe size O.D.  

(mm)

Tightening 

torque.  

(N·m)

Liquid 

pipe 

(mm)

Gas 

pipe 

(mm)

P32/40

ODø6.35 (1/4”)

14 - 18

ODø12.7 (1/2”)

49 - 61

ODø6.35 (1/4”)

14 - 18

ODø12.7 (1/2”)

49 - 61

17

26

P50

ODø9.52 (3/8”)

14 - 18*

ODø15.88 (5/8”)

49 - 61*

ODø6.35 (1/4”)

14 - 18

ODø12.7 (5/8”)

49 - 61

17

26

*  Connect the joint with the following pipes: Liquid and gas pipes of P50.

Apply refrigerating machine oil over the entire flare seat surface.

4.  Installing the refrigerant piping

B

C

D

Fig. 4-1

4.1.  Connecting pipes (Fig. 4-1)

•  When commercially available copper pipes are used, wrap liquid and gas pipes 

with commercially available insulation materials (heat-resistant to 100 °C or 

more, thickness of 12 mm or more).

•  The indoor parts of the drain pipe should be wrapped with polyethylene foam 

insulation materials (specific gravity of 0.03, thickness of 9 mm or more).

•  Apply thin layer of refrigerant oil to pipe and joint seating surface before 

tightening flare nut.

•  Use two wrenches to tighten piping connections.

•  Use refrigerant piping insulation provided to insulate indoor unit connections. 

Insulate carefully.

 Warning:

When installing the unit, securely connect the refrigerant pipes before 

starting the compressor.

Fig. 4-

 PKFY-P·VHM-E

4..  Positioning refrigerant and drain piping (Fig. 4-)

 PKFY-P·VHM-E

Gas pipe 

*  Indicates the condition with accessories mounted.

Liquid pipe

Drain hose (Effective length: 400)

Left-side piping knockout hole

Right-side piping knockout hole

Lower piping knockout hole

G

  Mount board 

1

45±2°

90°±0.5°

R0.4 - R0.8

øA

RG79D840H01_en.indd   6

2012/10/25 (木)   午後 4:10:31

Summary of Contents for City Multi PKFY-P

Page 1: ...DE INSTALACI N Para un uso seguro y correcto lea detalladamente este manual de instalaci n antes de montar la unidad de aire acondicionado MANUAL DE INSTALA O Para seguran a e utiliza o correctas lei...

Page 2: ...y precautions Indicates an action that must be avoided Indicates that important instructions must be followed Indicates a part which must be grounded Indicates that caution should be taken with rotati...

Page 3: ...the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor PKFY P VHM E Fig 3 2 A Mount board 1 B Indoor unit C Bottom left rear pipe hole 65 D...

Page 4: ...e marking on the mount board as a reference when adjusting the length of the embedded cooling pipe During construction give the length of the extruding pipes etc some leeway A Mount board 1 B Referenc...

Page 5: ...Move the indoor unit to the left and right and verify that the indoor unit is hung securely 5 Fasten by pushing the bottom part of the indoor unit onto the mount board 1 Fig 3 10 Check that the knobs...

Page 6: ...pply refrigerating machine oil over the entire flare seat surface 4 Installing the refrigerant piping B C D Fig 4 1 4 1 Connecting pipes Fig 4 1 When commercially available copper pipes are used wrap...

Page 7: ...ible 5 Wrap the pipe cover of the unit s liquid pipe and make sure that it covers the insulation material of the on site liquid pipe 6 The portion where the insulation material is joined is sealed by...

Page 8: ...Fig 5 2 1 Remove the drain cap Remove the drain cap by holding the bit that sticks out at the end of the pipe and pulling A Drain cap 2 Remove the drain hose Remove the drain hose by holding on to the...

Page 9: ...ransmission cables Types of transmission cable Shielding wire CVVS or CPEVS Cable diameter More than 1 25 mm2 Length Less than 200 m 2 M NET Remote control cables Types of remote control cable Shieldi...

Page 10: ...efore the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection button Make sure that wind is blown out 4 Press the Mode selection button and switch to the...

Page 11: ...related Products Directive 2009 125 EC This product is designed and intended for use in the residential commercial and light industrial environment Printed in Japan RG79D840H01 The product at hand is...

Reviews: