15
-
4.6 3D auto operation
Control the flap and louver by 3D AUTO button on the wireless remote control.
Air flow selection and air flow direction are automatically controlled, allowing the entire room to efficiently conditioned.
(1)
During Cooling and Heating (Including auto cooling and heating)
(a)
Air flow selection is determined according to room temperature and setting temperature.
(b)
Air flow direction is controlled according to the room temperature and setting temperature.
1)
When 3D auto operation starts
2)
When Room temp. – Setting temp. is
≤
_ 5ºC during cooling and when Setting temp. – Room temp. is
≤
_ 5ºC during
heating, the system switches to the following air flow direction control. After the louver swings left and right symmetrically
for 3 cycles, control is switched to the control in 3).
3)
After the flap swings for 5 cycles, control is switched to the control in 4).
4)
For 5 minutes, the following air flow direction control is carried out.
5)
After 5 minutes have passed, the air flow direction is determined according to the room temperature and setting
temperature.
(2)
During DRY Operation (including auto DRY operation)
At cooling
Air flow selection
Operation mode
AUTO
HI
MED
LO
At heating
Room temp. – Setting temp. >5˚C
Room temp. – Setting temp.
≤
_ 5˚C
Setting temp. – Room temp. >5˚C
Setting temp. – Room temp.
≤
_ 5˚C
HIGH POWER
AUTO
HI
MED
LO
HIGH POWER
AUTO
Flap
Louver
Cooling
Up/down Swing
Heating
Wide (fixed)
Center (fixed)
Flap
Louver
Cooling
Heating
Left/right Swing
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Flap
Louver
Cooling
Up/down Swing
Heating
Center (Fixed)
Wide (Fixed)
Flap
Louver
Cooling
Heating
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Operation mode
Room temp. – Setting temp.
≤
_ 2˚C
Setting temp. – Room temp.
≤
_ 2˚C
At heating
At cooling
Air flow direction contorol
2˚C < Setting temp. – Room temp.
≤
_ 5˚C
2˚C < Room temp. – Setting temp.
≤
_ 5˚C
Room temp. – Setting temp. > 5˚C
Setting temp. – Room temp. > 5˚C
The control in 4) continues.
Control returns to the control in 2).
Control returns to the control in 1).
The control in 4) continues.
Control returns to the control in 2).
Control returns to the control in 1).
Wide (Fixed)
Flap
Air flow selection
Louver
According to DRY operation.
Horizontal blowing (Fixed)