(12) Indoor fan motor protection
When the air conditioner is operating and the indoor fan motor is turned ON, if the indoor fan motor has operated at 300 rpm or
under for more than 30 seconds, the unit enters first in the stop mode and then stops the entire system.
(13) Serial signal transmission error protection
(a)
Purpose:
Prevents malfunction resulting from error on the indoor
↔
outdoor signals.
(b)
Detail of operation:
If the compressor is operating and a serial signal cannot be received from the indoor control with
outdoor control having serial signals continuously for 1 minute and 55 seconds, the compressor is
stopped.
After the compressor has been stopped, it will be restarted after the compressor start delay if a serial
signal can be received again from the indoor control.
(14) Rotor lock
If the motor for the compressor does not turn 1/12 revolution 0.044 seconds after it has been started, it is determined that a
compressor lock has occurred and the compressor is stopped.
(15) Outdoor fan motor protection
If the outdoor fan motor has operated at 75rpm or under for more than 30 seconds, the inverter and fan motor are stopped.