248
-
'17 • SCM-T-225
None
Power source system error
(Power source to remote control)
Keeps flashing 3-time flash
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't there any
loose connection of remote
control wires?
Isn't remote
control wire broken or
short-circuited?
Disconnect remote
control wires.
NO
Is DC15V or
higher detected between X-Y
of indoor unit terminal
block?
YES
YES
YES
NO
Is DC 24V or higher
between (Brown-Brown) of
transformer secondary
side?
Is DC180V
between
➀
-
➁
of CNW2
(FDE, FDUM:CNW1)?
FDEN Series
FDTC, FDE,
FDUM Series
YES
NO
NO
YES
NO
Correct.
Replace wires.
Replace remote control.
Defective indoor power
PCB
➞
Replace.
Defective indoor control
PCB
➞
Replace.
Replace transformer.
Defective indoor unit
PCB
➞
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Remote control wire
breakage/short-circuit
• Defective remote control
• Malfunction by noise
• Faulty indoor power PCB
• Broken harness
• Faulty indoor control PCB
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content