225
-
'17 • SCM-T-225
(ii) Outdoor unit
Models SCM71, 80
Remote control
Indoor control PCB
Outdoor
main PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED
Red LED
Keeps
flashing
Stays OFF
Keeps
flashing
2-time
flash
Installation, operation status • Higher outdoor heat exchanger temperature
Repair
266
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor
Replacement, repair
of temperature
sensor
Outdoor main PCB
*• Defective outdoor main PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
5-time
flash
Installation, operation status • Higher discharge temperature
Repair
267
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor
Replacement, repair
of temperature
sensor
Outdoor main PCB
*• Defective outdoor main PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
8-time
flash
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor, broken wire or poor
connector connection
Replacement, repair
of temperature
sensor
268
Outdoor main PCB
*• Defective outdoor main PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
8-time
flash
Outdoor air temperature
sensor
• Defective outdoor air temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
269
Outdoor main PCB
*• Defective outdoor main PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
8-time
flash
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
270
Outdoor main PCB
*• Defective outdoor main PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
1-time
flash
Outdoor main PCB,
compressor
• Current cut (Anomalous compressor over-current)
Replacement of
PCB
271 • 272
Installation, operation status • Service valve closing operation
Repair
Stay OFF
Keeps
flashing
4-time
flash
Outdoor main PCB
• Anomalous outdoor main PCB commuication
Replacement of
PCB
273
Outdoor sub PCB
• Anomalous outdoor sub PCB commuication
Stays OFF
Keeps
flashing
2-time
flash
Outdoor sub PCB
• Defective active filter
Repair
PCB replacement
274
Stays OFF
Keeps
flashing
ON
Fan motor
• Defective fan motor
Replacement
275
Outdoor main PCB
• Defective outdoor main PCB
Stays OFF
Keeps
flashing
1-time
flash
Power transistor error
(outdoor main PCB)
• Power transistor error
Replacement of
PCB
276
Stays OFF
Keeps
flashing
8-time
flash
Outdoor suction pipe sensor
• Defective suction pipe temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
277
Outdoor sub PCB
• Defective outdoor sub PCB (Defective temperature sensor input circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
2-time
flash
Operation status
• Shortage in refrigerant quantity
Repair
278
Installation status
• Service valve closing operation
Service valve
opening check
Stays OFF
Keeps
flashing
3-time
flash
• Overload operation
• Overcharge
• Compressor locking
• Current safe stop
Replacement
279
Stays OFF
Keeps
flashing
2-time
flash
Compressor, outdoor main
PCB
• Anomalous compressor startup
Replacement
280
Stays OFF
Keeps
flashing
7-time
flash
Compressor
• Anomalous compressor rotor lock
Replacement
281
Note (1) * mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing the
part, it is judged consequently that the replaced part was defective.