11. Operation permission/prohibition control
The air conditioner operation is controlled by DIP switch SW2-3 on the interface kit board and inputting the external signal into
the CnT.
(1)
The operation mode is switched over between Permission and Prohibition by DIP switch SW2-3 on the interface
kit control board.
(2)
When the CnT input is set to ON (Operation permission)
(a)
The air conditioner can be operated or stopped by the remote control signal.
(When the "CENTER" mode is set, the operation can be controlled only by the center input.)
(b)
When the CnT input is changed from OFF to ON, the air conditioner operation mode is changed depending on the status of
the DIP switch SW2-1 on the interface kit board.
(3)
When the CnT input is set to OFF (Prohibition)
(a)
The air conditioner cannot be operated or stopped by the remote control signal.
(b)
The air conditioner operation is stopped when the CnT input is changed from ON to OFF.
(4)
When the operation permission / prohibition mode is set to effective by the indoor function setting selected by
the remote control, the operation depends on (1) above.
When the DIP switch SW2-3 is ON
Normal operation is enable (when shipping)
When CnT input is set to ON, the operation starts and
if the input is set to OFF, the operation stops.
For the CnT and remote control inputs, the input which
is activated later has priority and can start and stop the
operation.
When the DIP switch SW2-3 is OFF
Permission / Prohibition mode
When CnT input is set to ON, the operation mode is
changed to permission and if input is set to OFF the
operation is prohibited.
When the DIP switch SW2-1 is ON
The signal (a) above starts the air conditioner.
(Shipping status)
When the DIP switch SW2-1 is OFF
When the CnT input is set to ON, the air conditioner
starts operation. After that, the operation of the air
conditioner depends on (a) above. (Local status)