11
-
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
Function
setting
(Note3)
(Note1)
(Indoor unit function)
Only when plural indoor units are connected
Indoor No. selection
AIRCON NO.
If to change re-set with other indoor
unit, push
button, and indoor selection indication
(for example: I/U 000) is set back.
The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours, then the indoor unit will be stopped by compulsion after 24 hours.
To be reset for pro3.0
°
C increase in temperature during heating.
To be reset for pro2.0
°
C increase in temperature during heating.
To be reset for pro1.0
°
C increase in temperature during heating.
When heating thermostat is OFF, fan speed is low speed.
When heating thermostat is OFF, fan speed is set speed.
When heating thermostat is OFF, fan speed is operated intermittently.
When heating thermostat is OFF, the fan is stopped.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set "FAN OFF" when the indoor unit's thermistor is working.
Change of indoor heat exchanger temperature to start frost prevention control.
Working only with the single split series.
To control frost prevention, the indoor fan tap is raised.
Drain pump is run during cooling and dry.
Drain pump is run during cooling, dry and heating.
Drain pump is run during cooling, dry, heating and fan.
Drain pump is run during cooling, dry and fan.
After cooling is stopped or cooling thermostat is OFF, the fan does not perform extra operation.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for half an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for an hour.
After cooling is stopped or cooling thermostat is OFF, the fan perform extra operation for six hours.
After heating is stopped or heating thermostat is OFF, the fan does not perform extra operation.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is OFF, the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is OFF, he fan perform extra operation for six hours.
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes with low fan speed after
twenty minutes' OFF.
During heating is stopped or heating thermostat is OFF, the fan perform intermittent operation for five minutes with low fan speed after
five minutes' OFF.
To be reset pro2.0
°
C increase in return air temperature of indoor unit.
To be reset pro1.5
°
C increase in return air temperature of indoor unit.
To be reset pro1.0
°
C increase in return air temperature of indoor unit.
To be reset producing -1.0
°
C increase in return air temperature of indoor unit.
To be reset producing -1.5
°
C increase in return air temperature of indoor unit.
To be reset producing -2.0
°
C increase in return air temperature of indoor unit.
When stop signal is inputed from remote on-off terminal "CNT-6", all indoor units are stopped immediately.
If you change the indoor function "04 ",
you must change the remote control function "14 " accordingly.
You can select the louver stop position in the four.
The louver can stop at any position.
Permission/prohibition control of operation will be valid.
Note1: Fan setting of "HIGH SPEED"
Indoor unit air flow setting
Fan tap
HI-MID-LO
HI-LO
HI- MID
FAN
SPEED
SET
HIGH
SPEED1 2
UHI - HI- MID UHI - MID
UHI- HI
Initial function setting of some indoor unit is "HIGH SPEED".
STANDARD
2
Indoor unit functions (I/U FUNCTION
)