background image

3

3. Installation diagram

2.1. Outdoor unit

•  Where it is not overly exposed to strong winds.

•  Where airflow is good and dustless.

•  Where neighbors are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of operation sound 

or vibration.

•  Where there is no risk of combustible gas leakage.

•  If installing the unit in a location high above the ground, be sure to secure the unit 

legs.

•  Where it is at least 10 ft. (3 m) away from the antenna of TV set or radio. Opera

-

tion of the air conditioner may interfere with radio or TV reception in areas where 

reception is weak. An amplifier may be required for the affected device.

•  Install the unit horizontally.

•  Please install it in an area not affected by snowfall or blowing snow. In areas with 

heavy snow, please install a canopy, a pedestal and/or baffle boards.

Note: 

•  It is advisable to make a piping loop near outdoor unit so as to reduce vibration.

•  For increased efficiency, install the outdoor unit in a location where continuous 

direct sunlight or excessive water can be avoided as much as possible.

 Caution:

When operating the air conditioner in low outside temperature, be sure to follow the 

instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side may be ex

-

posed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet side facing the 

wall and a baffle board on the air outlet side.

Avoid the following places for installation where air conditioner trouble is liable to 

occur.

•  Where flammable gas could leak.

•  Where there is an excessive amount of machine oil in the air.

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.

The outdoor unit produces condensate during the heating operation. Select the in-

stallation place to ensure to prevent the outdoor unit and/or the grounds from being 

wet by drain water or damaged by frozen drain water.

2. Selecting the installation location

When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 25/32 in. (20 mm) or thicker between the wall 

and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.

Units should be installed by licensed contractor accordingly to local code requirement.

Note:

When operating the air conditioner in low outside temperature, be sure to follow the instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side may be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.

•  To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit.

Drain piping for outdoor unit

Install the unit horizontally.

Do not use drain socket in cold regions. Drain may freeze and make the fan stop.

The outdoor unit produces condensate during the heating operation. Select the installation place to ensure to prevent the outdoor unit and/or the grounds from being wet 

by drain water or damaged by frozen drain water.

Basically open 4 in. 

(100 mm) or more without 

any obstruction in front and 
on both sides of the unit.

Open 2 sides of left, 
right, or rear side.

8 in. 

(200 mm) 

or more

4 in. 

(100 mm) 

or more

14 in. 

(350 mm) 

or more

4 in. 

(100 mm) 

or more

31-1/2

19-11/16

13-9/16

11-1/4

12-12-3/4

1-9/16

800
500

285

150

40

304-325

5-

15/16

Unit: inch

Air outlet

Air outlet

Air inlet

Air inlet

2-3/8 × 13/16 slot

Unit: mm

344.5

2-10 × 21 slot

NTXSKS09A112A

NTXSKS12A112A

NTXSKS15A112A

BH79A499H01_EN.indd   3

2018/09/04   16:49:03

Summary of Contents for TRANE NTXSKS09A112A

Page 1: ...le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners NTXSKS09A112A NTXSKS12A112A NTXSKS15A112A POUR L INSTALLATEUR PARA EL INSTALADOR FOR INSTALLER Français Español En...

Page 2: ...ould cause a fire or an electric shock When installing or relocating the unit make sure that no substance other than the specified refrigerant R410A enters the refrigerant circuit Any foreign substances in the refrigerant circuit can cause abnormal pressure rise or an explosion Do not discharge the refrigerant into the atmosphere Check that the refrig erant gas does not leak after installation has...

Page 3: ...here there is high frequency or wireless equipment The outdoor unit produces condensate during the heating operation Select the in stallation place to ensure to prevent the outdoor unit and or the grounds from being wet by drain water or damaged by frozen drain water 2 Selecting the installation location When the piping is to be attached to a wall containing metals tin plated or metal netting use ...

Page 4: ... of specified thickness table on the above Excessive insulation may cause incorrect installation of the indoor unit and too little insulation may cause condensate to form The unit has flared connections on both indoor and outdoor sides Remove the valve cover from the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Be careful not to crush or ove...

Page 5: ... D Fig 4 4 4 4 Purging procedures and leak test 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit 3 Run the vacuum pump 15 minutes or more 4 Check the vacuum with the gauge manifold valve then close it and shut off the vacuum pump 5 Leave as it is for...

Page 6: ...ure Be careful not to contact connecting cable with piping Caution Use care not to make miswiring Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move Warning Be sure to attach the service panel of the indoor unit securely If it is not attached correctly it could result in a fire or an electric shock due to dust ...

Page 7: ...local and national code 2 Use copper supply wires 3 Use wires rated 600V or more for the power supply cables and the indoor outdoor unit connecting cables 4 Install an earth longer than other cables 6 1 Gas charge Fig 6 1 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refrigerant gas cylinder 3 Replenish specified amount of refrig...

Page 8: ...rigérant spécifié R410A ne pénètre dans le cir cuit de réfrigération La présence d une substance étrangère dans le circuit de réfrigération peut pro voquer une augmentation anormale de la pression voire une explosion Ne libérez pas le réfrigérant dans l atmosphère Vérifiez l absence de fuites de gaz réfrigérant une fois l installation terminée En cas de fuite de réfrigé rant pendant l installation...

Page 9: ... sulfurique source thermale En présence d équipements haute fréquence ou sans fil L unité extérieure produit de la condensation lors du mode de chauffage Choisir l endroit où le climatiseur sera monté de façon à éviter à l unité extérieure et ou aux sols d être mouillés par les condensats ou endommagés par le gel des condensats 2 Choisir l emplacement de l installation NTXSKS09A112A NTXSKS12A112A ...

Page 10: ...urs un matériau d isolation de l épaisseur spécifiée tableau à droite Une isolation trop épaisse peut être à l origine d une installation incorrecte de l unité interne une isolation trop fine peut provoquer la formation de condensation L unité comporte des raccordements évasés sur les faces intérieure et extérieure Retirez le couvercle de vanne de l unité externe et raccordez le tuyau Les conduite...

Page 11: ...es de purge et test de contrôle des fuites 1 Retirez le bouchon de l ouverture de service du robinet d arrêt du côté du tuyau de gaz de l unité externe 2 Raccordez la vanne du collecteur à jauge et la pompe à vide à l ouverture de service du robinet d arrêt du côté du tuyau de gaz de l unité externe 3 Faites fonctionner la pompe à vide pendant 15 minutes minimum 4 Contrôlez la dépression ainsi obt...

Page 12: ...on Faites attention de brancher les fils correctement Serrer fermement les vis des bornes pour les empêcher de se desserrer Puis tirer légèrement sur les fils pour vous assurer qu ils ne bougent pas Avertissement Veiller à visser correctement le panneau de service à l appareil extérieur Si le panneau de service n est pas bien installé de l eau des poussières etc pourraient pénétrer à l intérieur d...

Page 13: ...ucher les bornes S1 S2 et S3 lorsque l alimentation est sous tension S il faut placer un sectionneur entre les appareils extérieur et intérieur en utiliser un de type tripolaire 6 Entretien 6 1 Charge de Gaz Fig 6 1 1 Raccorder le tuyau de gaz au port de service de la vanne d arrêt à 3 voies 2 Purger l air du tuyau raccordé au tuyau de gaz réfrigérant 3 Ajouter la quantité spécifiée de réfrigérant...

Page 14: ...l circuito de refrigeración puede provocar una elevación anómala de la presión o una explosión No descargue el refrigerante en el ambiente Una vez acabada la instala ción compruebe que no haya fugas de gas refrigerante Si se producen fugas de refrigerante durante la instalación ventile la habitación Si el refrigerante entra en contacto con una llama podría generarse gas nocivo Si se produjeran pér...

Page 15: ...haya gas sulfúrico como en zonas de baños termales Donde haya algún equipo inalámbrico o de alta frecuencia La unidad exterior provoca condensación durante la función de calefacción Selec cione un lugar para la instalación en el que la unidad exterior y las tomas de tierra no se humedezcan con agua de drenaje ni se dañen debido a la congelación de este agua de drenaje 2 Selección del lugar de inst...

Page 16: ... tabla de la derecha El uso excesivo de aislante puede causar una instalación incorrecta de la unidad interior y el uso de una cantidad insuficiente de aislante puede provocar la condensación Las unidad tiene conexiones abocinadas en los lados interior y exterior Retire la tapa de la válvula de la unidad exterior y a continuación conecte la tubería Las tuberías de refrigerante se emplean para cone...

Page 17: ...ón situada en el lado de la tubería de gas de la unidad exterior 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vacío durante 15 minutos o más 4 Compruebe el vacío con la válvula colectora de manómetro cierre luego esta válvula y detenga la ...

Page 18: ...gún las medidas que aparecen en la figura Tenga cuidado de que el cable de conexión no haga contacto con los tubos Cuidado Asegúrese de no realizar un mal cableado Apriete firmemente los tornillos de la terminal para evitar que se aflojen Tras apretarlos tire ligeramente de los cables para confirmar que no se muevan Atención Asegúrese de fijar firmemente el panel de servicio de la unidad exterior ...

Page 19: ...para los cables de la fuente de alimentación y los cables de conexión de las unidades inte rior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables 6 1 Carga de gas Fig 6 1 1 Conecte el cilindro de gas a la abertura de servicio de la válvula de parada de 3 vías 2 Purgue el aire del tubo o conducto procedente del cilindro de gas refrigerante 3 Vuelva a llenar la canti...

Page 20: ...his manual before handing it to the customer HEAD OFFICE 1340 SATELLITE BOULEVARD SUWANEE GA 30024 USA MITSUBISHI ELECTRIC TRANE HVAC US LLC Printed in Mexico BH79A499H01_cover4 indd 20 2018 08 31 14 37 18 Publication No DL SVN007A XX Published Nov 2018 BH79A499H01 ...

Reviews: