3
- 5
3.3 I/O Signals to the Programmable Controller CPU
3.3.2 Functions of I/O signals
3
SPECIFICATIONS
3.3.2
Functions of I/O signals
The following table shows the I/O signals of the QD63P6.
I/O numbers (X/Y) and buffer memory addresses in Description describe only for channel
1.
For I/O numbers (X/Y) and buffer memory addresses from channels 2 to 6, refer to Section
3.3.1 and Section 3.4.1.
(1) I/O signals
Table 3.5 I/O signals
Device
No.
Signal name
QD63P6
Programmable controller
CPU
Description
X00
Module READY
•Turns ON at reset or power-ON of the programmable controller CPU when counting
of the QD63P6 is ready, and the count processing is performed.
•Turns OFF when watchdog timer error or an error which affects the system (error
code: 810 to 850) occurs.
•The count processing is not performed when the module READY (X00) is OFF.
•This signal is used for an interlock of sequence programs.
X01
CH1
Counter value large
•Turns ON when the present value A (Un\G10 and 11)/present value B (Un\G200 and
201) Coincidence detection point setting (Un\G6 and 7).
•Turns OFF when the present value A (Un\G10 and 11)/present value B (Un\G200 and
201) Coincidence detection point setting (Un\G6 and 7).
•For details of the general operation, refer to Section 5.3.
X06
CH2
X0B
CH3
X10
CH4
X15
CH5
X1A
CH6
In preparation
Ready
Status of the QD63P6
Module READY
(X00)
Performed by the QD63P6.
Performed by the sequence program.
OFF
ON
Watchdog timer error or
an error which affects the system
Performed by the QD63P6.
Performed by the sequence program.
Coincidence detection
point setting
(Un\G6 and 7)
Present value A
(Un\G10 and 11)
Counter value large
(X01)
Counter value
coincidence
(X02)
Counter value small
(X03)
Coincidence signal
reset command
(Y01)
ON
OFF
OFF
OFF
ON
ON
t*
100
100
101
102
99
98
0
OFF
OFF
ON
OFF
0
1
OFF
ON
t*
ON
Immediately after power-ON or reset
of the programmable controller CPU
* t 2ms