4
- 7
4.4 Wiring
4.4.1 Wiring precautions
4
PROCEDURES AND SETTINGS BEFORE
OPERATION
(7) To conform the wiring to the EMC and Low Voltage Directives, ground
the shielded twisted pair cables to a control panel with the AD75CK
cable clamp (manufactured by Mitsubishi Electric Corporation).
Figure 4.4 AD75CK cable clamp
[Grounding shielded twisted pair cable with the AD75CK]
Figure 4.5 Grounding shielded twisted pair cable with the AD75CK
Maximum four shielded twisted pair cables whose external dimension is around 7 mm
(0.28 inch) can be grounded with the AD75CK.
(For details, refer to the AD75CK-type Cable Clamping Instruction Manual (IB-
68682).)
20cm (7.87inch)
20cm (7.87inch)
to 30cm (11.81inch)
to 30cm (11.81inch)
In a control panel
QD63P6
20cm (7.87inch)
to 30cm (11.81inch)
AD75CK
Shielded twisted pair cable
Shield
Screw for fixing to control panel
(M4)
Grounding terminal
Grounding terminal fixing screw
(M4 8)