35
OCH750A
Abnormal point and detection method
Judgment and action
UL
(1300)
Abnormal low pressure (63L worked)
Abnormal if 63L is worked (under −4 PSIG
[−0.03 MPa]) during compressor operation.
63L: Low pressure switch
1
Stop valve of outdoor unit is
closed during operation.
2
Disconnection or loose con-
nection of connector (63L) on
outdoor controller board
3
Disconnection or loose connec-
tion of 63L
4
Defective outdoor controller
board
5
Leakage or shortage of refriger-
ant
6
Malfunction of linear expansion
valve
1
Check stop valve.
2
–
4
Turn the power off and on again to check
if F3 is displayed on restarting.
If F3 is displayed, follow the F3 process-
ing direction.
5
Correct to proper amount of refrigerant.
6
Check linear expansion valve. Refer to "10-5.
HOW TO CHECK THE PARTS".
Cause
UP
(4210)
Compressor overcurrent interruption
Abnormal if overcurrent DC bus or com-
pressor is detected after compressor starts
operating for 30 seconds.
E0
or
E4
Remote controller transmission
error(E0)/signal receiving error(E4)
1
Abnormal if main or sub remote control-
ler cannot receive normally any trans-
mission from indoor unit of refrigerant
address “0” for 3 minutes.
(Check code: E0)
2
Abnormal if sub-remote controller could
not receive any signal for 2 minutes.
(Check code: E0)
1
Abnormal if indoor controller board can
not receive any data normally from
remote controller board or from other
indoor controller board for 3 minutes.
(Check code: E4)
2
Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Check code: E4)
1
Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2
Set one of the remote controllers “main”.
If there is no problem with the action above.
3
Check wiring of remote controller.
• Total wiring length: max. 1640 ft [500 m]
(Do not use cable with 3 or more cores.)
• The number of connecting indoor units:
max.16 units
• The number of connecting remote control-
ler: max. 2 units
If the cause of trouble is not any of
1
–
3
above, diagnose
4
–
6
by remote controllers.
a) When “OK” is displayed, remote control-
lers have no problem.
Turn the power off, and on again to check.
If abnormality occurs again, replace
indoor controller board.
b) When “NG” is displayed, replace remote
controller.
c) When “E3” or “ERC” is displayed, noise
may be causing abnormality.
Note: If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
1
Contact failure at transmission
wire of remote controller
2
All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
3
Miswiring of remote controller
4
Defective transmitting receiving
circuit of remote controller
5
Defective transmitting receiv-
ing circuit of indoor controller
board of refrigerant address “0”.
6
Noise has entered into the
transmission wire of remote
controller.
E1
or
E2
Remote controller control board
1
Abnormal if data cannot be read nor-
mally from the nonvolatile memory of the
remote controller control board.
(Check code: E1)
2
Abnormal if the clock function of remote
controller cannot be operated normally.
(Check code: E2)
1
Defective remote controller
1
Replace remote controller.
Check Code
1
Stop valve of outdoor unit is
closed.
2
Decrease of power supply voltage
3
Looseness, disconnection or
converse of compressor wiring
connection
4
Defective fan of indoor/outdoor
units
5
Short cycle of indoor/outdoor
units
6
Defective input circuit of
outdoor controller board
7
Defective compressor
8
Defective outdoor power circuit
board
9
Dip switch setting difference of
outdoor controller circuit board
1
Open stop valve.
2
Check facility of power supply.
3
Correct the wiring (U
•
V
•
W phase) to com-
pressor. Refer to "10-8. TEST POINT
DIAGRAM". (Outdoor power circuit board).
4
Check indoor/outdoor fan.
5
Solve short cycle.
6
Replace outdoor controller circuit board.
7
Check compressor. Refer to "10-5. HOW TO
CHECK THE PARTS".
Before the replacement of the outdoor controller cir-
cuit board, disconnect the wiring to compressor from
the outdoor power circuit board and check the output
voltage among phases, U, V, W, during test run. No
defect on board if voltage among phases (U-V, V-W
and W-U) is same. Make sure to perform the voltage
check with same performing frequency.
8
Replace outdoor power circuit board
9
Check the dip switch setting of outdoor con-
troller circuit board
Summary of Contents for PUZ-HA24NHA1
Page 13: ...13 OCH750A 6 OUTLINES AND DIMENSIONS Unit mm in PUZ HA24NHA1 ...
Page 14: ...14 OCH750A Unit mm in PUZ HA30NKA PUZ HA36NKA 1 1 1 ...
Page 15: ...15 OCH750A Unit mm in PUZ HA42NKA1 1 1 1 ...
Page 16: ...16 OCH750A 7 WIRING DIAGRAM PUZ HA24NHA1 ...
Page 17: ...17 OCH750A PUZ HA30NKA PUZ HA36NKA ...
Page 18: ...18 OCH750A PUZ HA42NKA1 ...
Page 127: ...127 OCH750A ...