126
OCH750A
[1:1]
Refrigerant
address=00
[Twin]
Refrigerant
address=00
Outdoor
unit
Indoor unit
02
Indoor unit
01
Outdoor
unit
Remote
controller
Remote
controller
Indoor unit
01
■
Refrigerant address
Single refrigerant system
In the case of single refrigerant system, the refrigerant address
is "00" and no operation is required.
Simultaneous twin, triple units belong to this category
(single refrigerant system).
Multi refrigerant system (group control)
Up to 16 refrigerant systems (16 outdoor units) can be con-
nected as a group by 1 remote controller. To check or set the
refrigerant addresses.
Refrigerant
address
00
Refrigerant
address
01
Refrigerant
address
02
Refrigerant
address
15
Outdoor
unit
Indoor unit
01
Outdoor
unit
Indoor unit
01
Outdoor
unit
Indoor unit
01
Outdoor
unit
Indoor unit
01
Remote
controller
15-10. REQUEST CODE
Details on the operation data including each thermistor temperature and error history can be confirmed with the remote controller.
Check menu
Cursor
Service menu: MENU
Error history
Diagnosis
Smooth maintenance
Request code
Select "Request code" with the F1 or F2 button, and press
the [SELECT] button.
Select "Check" with the F1 or F2 button, and press the [SELECT] button.
2. Set the Refrigerant address and Request code.
Select the item to be changed with the F1 or F2 button.
Select the required setting with the F3 or F4 button.
■
<Ref.address>setting [ 0 ] – [ 15 ]
■
<Request code>setting
Press the [SELECT] button, Data will be collected and displayed.
F1
F2
F3
F4
MENU
ON
OFF
RETURN SELECT
HOLD
Request code
Request: SELECT
Request: SELECT
Request code
Ref.address
Request code
Ref.address
Request code
Cur.
–
+
–
+
Cur.
–
+
Request code: 004
Discharge temperature: 69˚C
1. Select "Service" from the Main menu, and press the [SELECT] button.
F1
F2
F3
F4
MENU
ON
OFF
RETURN SELECT
HOLD
Summary of Contents for PUZ-HA24NHA1
Page 13: ...13 OCH750A 6 OUTLINES AND DIMENSIONS Unit mm in PUZ HA24NHA1 ...
Page 14: ...14 OCH750A Unit mm in PUZ HA30NKA PUZ HA36NKA 1 1 1 ...
Page 15: ...15 OCH750A Unit mm in PUZ HA42NKA1 1 1 1 ...
Page 16: ...16 OCH750A 7 WIRING DIAGRAM PUZ HA24NHA1 ...
Page 17: ...17 OCH750A PUZ HA30NKA PUZ HA36NKA ...
Page 18: ...18 OCH750A PUZ HA42NKA1 ...
Page 127: ...127 OCH750A ...