7
OCH760
Branch box
5-branches
(MAX. 5 units)
Number of branches
Indoor unit that
can be connected
( )
Note:
A maximum of 3 branch boxes can be connected to 1 outdoor unit.
Select a model according to the connection method.
2-branch pipe (joint): Optional parts
In the case of using 1- branch box
In the case of using
2 or 3 branch boxes
No need
Model name
Connection method
flare
brazing
MSDD-50AR-E
MSDD-50BR-E
Option
Optional accessories of indoor units and outdoor units are available.
PAC-MK54BC
3-branches
(MAX. 3 units)
PAC-MK34BC
2-2. SYSTEM CONSTRUCTION (BRANCH BOX SYSTEM)
Outdoor unit
10HP
12HP
P250YBM
P300YBM
Applicable indoor unit
Capacity
kW unit: Type 15 to Type 50
Number of units
2 to 12 units
Total system capacity range
50 to 130% of outdoor unit capacity
(14.0 to 36.4 kW)
o
50 to 130% of outdoor unit capacity
(16.8 to 43.5 kW)
o
Branch box that can be connected Number of units
1 to 3 units*
Connectable indoor unit lineup
Model type
Model name
P15
P18
P20
P22
P25
P35
P42
P50
P60
P71
P80
Wall mounted
MSZ-EF·VG-E2
●
●
●
●
●
MSZ-EF·VGK-
E1
●
●
●
●
●
MSZ-AP·VG(K)
●
●
MSZ-AP·VG(K)-
E2/E7
●
●
●
MSZ-LN·VG2
●
●
●
MSZ-FH·VE2
●
●
●
Floor standing
MFZ-KT·VG
●
●
●
Note: The lineup of a connectable indoor unit depends on a district/areas/country.
* The maximum total capacity of the units that can be
connected to each branch box is 20.2kW