Check code
Abnormal points and detection methods
Causes and checkpoints
If overcurrent of compressor is detected within 30 seconds since the
compressor starts operating.
Closed stop valve
Decrease of power supply voltage
Looseness, disconnection or converse of compressor
wiring connection
Incorrect DIP-SW setting of model selection on the
outdoor controller board
Defective compressor
Defective outdoor power circuit board
●Diagnosis of defects
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
4100
(UF)
Compressor current interruption (Locked compressor)
Chart 1 of 2
Yes
Yes
Yes
No
No
No
Is the stop valve
(liquid/gas)
fully
open?
Is the power supply voltage normal?
Is it connected properly?
Open the stop valve
(liquid/gas) fully
.
Ensure power supply from the facility.
Connect the wiring properly,
then turn the power back ON.
Check the stop valve.
Check the power supply voltage.
Turn the power OFF to check for
looseness, disconnection or phases of the
compressor wiring.
Check whether the model selection switch is
set correctly on the outdoor multi controller
circuit board or not.
Continue to the next page.
56
57
OCH760