115
OCH760
9-6. EXAMPLE EXTERNAL WIRING DIAGRAM FOR A BASIC SYSTEM
Outdoor
unit
Group operation
Remote controller wire
Pull box
Indoor unit
Breaker for Wiring
and Current Leakage
Breaker for Wiring
and Current Leakage
1.25 mm
2
× 2
Outdoor
unit
Pull box
MA
RC
Breaker for Wiring
and Current Leakage
Breaker for Wiring
and Current Leakage
1.25 mm
2
or more
(Shield cable)
3N 380-400-415 V, 50 Hz
■
Example of system when using a Branch Box
■
Example of system when using an M-NET controller
<When power is supplied to outdoor unit and branch box separately>
~
/N 220-230-240 V, 50 Hz
~
Transmission cable
CITY MULTI series
indoor unit
CITY MULTI series
indoor unit
CITY MULTI series
indoor unit
CITY MULTI series
indoor unit
CITY MULTI series
indoor unit
MA
RC
MA
RC
Branch Box
A-control
indoor unit
MA
RC
A-control
indoor unit
MA
RC
A-control
indoor unit
MA
RC
0.3–1.25 mm
2
(0.75–1.25 mm
2
)
MA-RC cable
Outdoor
unit
Pull box
MA
RC
Breaker for Wiring
and Current Leakage
Breaker for Wiring
and Current Leakage
1.25 mm
2
or more
(Shield cable)
3N 380-400-415 V, 50 Hz
~
/N 220-230-240 V, 50 Hz
~
Transmission cable
MA
RC
Branch Box
A-control
indoor unit
MA
RC
A-control
indoor unit
MA
RC
0.3–1.25 mm
2
(0.75–1.25 mm
2
)
MA-RC cable
<When power is supplied to branch box from the outdoor unit>
B1
B2
;
Branch Box
A-control
indoor unit
MA
RC
A-control
indoor unit
MA
RC
A-control
indoor unit
MA
RC
3N ~ 380-400-415 V, 50 Hz
/N 220-230-240 V, 50 Hz
~