7-2. REFRIGERANT SYSTEM DIAGRAM
Refrigerant flow in cooling
Refrigerant flow in heating
Service port
Strainer
Ball valve
Refrigerant
Gas pipe
<280: 7/8, 335: 1>
4 way valve
Thermistor (TH6)
<Suction pipe>
Low pressure
sensor (63LS)
Check valve
<Low pressure>
Capillary
tube 2
Restrictor
valve
Solenoid
valve(SV1)
Strainer Oil separator
Strainer
Solenoid
valve (SV3)
Thermistor (TH7)
<Ambient>
Check valve
<High pressure>
Compressor
Distributor
Thermistor (TH3)
<Outdoor liquid pipe>
Thermistor (TH4)
<Compressor>
High pressure
sensor (63HS)
High pressure
switch (63H)
Strainer
Strainer
Strainer
Strainer
LEV-A
LEV-B
HIC
Thermistor (TH2)
<HIC pipe>
Stop valve
Service port
Capillary
tube 1
<280: 3/8, 335: 1/2>
Accumulator
Refrigerant
Liquid pipe
Strainer
Outdoor unit
Capillary tube 1
Capillary tube 2
PUMY-P250/300YBM
ø2.4×ø0.8×L600
ø4.0×ø3.0×L220
Unit: mm
Note:
When connecting the CONNECTION KIT (PAC-LV11M-J) and an M-series indoor unit, refer to the
installation manual for the CONNECTION KIT.
Refrigerant piping specifications <dimensions of flared connector>
Item
Capacity
Liquid piping
Gas piping
Indoor unit
P15, 20, 25, 32, 40, 50
ø6.35 <1/4>
ø12.7 <1/2>
P63, 80, 100, 125, 140
ø9.52 <3/8>
ø15.88 <5/8>
P200
ø9.52 <3/8>
ø19.05 <3/4>
P250
ø9.52 <3/8>
ø22.2 <7/8>
Outdoor unit
P250
ø9.52 <3/8> *
ø22.2 <7/8>
P300
ø12.7 <1/2>
ø25.4 <1>
* Use ø12.7 when the farthest piping length is longer than 90 m or PEFY-P200 or/and 250 is/are connected.
Unit: mm <in>
7-2-1. Connection without Branch box